Atena Easy Addressable Fire Alarm Panel – Installation and Programming Manual
46
7.6.4 Panel General Settings
In this submenu the installer can make some adjustments for the panel performance.
To access the PANEL SETTINGS submenu, enter in the
installer’s menu - 6. GENERAL SETTING - 6.4) PANEL
SETTINGS. The screen displays:
7.6.5 Delay
Т1
In this submenu the installer sets the time to Delay T1. T1 is the time delay needed for reaction of the security
personnel on the protected site. T1 provides a time delay for the personnel to go to the zone in fire alarm and to check
the situation. The operation of time delays T1 and T2 are described with the algorithm below.
To access the DELAY T1 submenu, enter in the
installer’s menu - 6. GENERAL SETTING - 6.5) DELAY T1. The
screen displays:
Use the up and down arrows to set the delay T1. The time interval is
in range 0 - 60 sec.
Confirm the settings with ‘ENTER’ button.
7.6.6 Sounders Mode
In this submenu the installer sets the sounders operation mode.
To access the SOUNDERS MODE submenu, enter in the
installer’s menu - 6. GENERAL SETTING - 6.6) SOUNDERS
MODE. The screen displays:
Use the functional buttons to set:
(1) ALARM TONE*
– Set the alarm type sound. Enter the submenu
and use the up/ down arrow buttons to select a number from 1 to 32
for the alarm sound
– the reference parameters for the selected
sound are listed on the last row of the screen.
(2) EVACUATE TONE*
– Set the evacuation type sound. Enter the
submenu and use the up/ down arrow buttons to select a number
from 1 to 32 for the evacuation sound
– the reference parameters for the selected sound are listed on the last row of
the screen.
* Note:
The main tone type for sounders is 27 with main sound frequency 2500Hz.
(3) EVACUATE SETTINGS
– The menu button is active only in ZONAL operation mode. Press it to make the following
evacuation settings for sounders operation.
(1) LANGUAGE
- Press to set the language. Every
pressing of the button changes the currently used
language for the menus.
(2) + Brightness
- Press to increase the brightness of the
screen back light. The maximum value is 20.
(3) - Brightness
- Press to decrease the brightness of the
screen back light. The minimum value is 0.
(4) MORE>>
- Press to switch to other panel settings.
Confirm all settings with pressing ENTER button.
(1) Earth Fault
- Press to enable/ disable the Earth
Fault indication. When the Earth Fault indication is
enabled you have to set a jumper to Earth Fault
terminals on the control panel PCB.
(2) BATTERY
- Press to enable/ disable the
Accumulator Battery Fault Indication. When the
Accumulator Battery Fault Indication is enabled the
panel will monitor the internal battery resistance Ri. In
normal operation Ri<0.3Ω. If Ri>0.3Ω, the panel will alert
for Batt
ery fault with message in Faults menu ‘Battery
High
Resistance’. The installer has to change the
accumulator battery with new.
(3) BUZZER
- Press to enable/ disable the buzzer
signalization.
(4) << BACK
- Press to switch back to previous settings.
Confirm all settings with pressing ENTER button.