Mains pro 1.6.1 Global Guide
67
12.3.21 !TrpEndImp
Inverse impulse at the end of the TRIP state. The output is normally deactivated during operation of the unit.
The output activates at the end of the
(i.e. after successful
is performed)
for period given by the parameter
.
In case of subsequent trip in the moment of the output activation, the countdown of the Imp Len delay is not
interrupted and the output stays activated for the complete Imp Len period. If in that period the TRIP state is
terminated again, the activation period is prolonged to Imp Len from the latest
. If during
TRIP state the unit is disabled by the input
, the output TrpEndImp is activated, same as in
case of a successful Fault reset.
The output can generally be used for closing the circuit breaker by the ON coil.
12.3.22 InternFail
Immediate signaling relay – internal failures; closes immediately in case of internal software failure, including
watchdog activation. Relay opens in case that all observed failures are not active, but no sooner than after
from its activation. If the relay is closed during trip activation, it opens no sooner than Basic:
Imp Len time is up. Fault reset, performed either by pressing the Fault reset button or through binary input, has
no influence on this output.
12.3.23 !InternFail
Inverse immediate signaling relay – internal failures; opens immediately in case of internal software failure,
including watchdog activation. Relay closes in case that all observed failures are not active, but no sooner than
after
from its activation. If the relay is open during trip activation, it closes no sooner than
Basic: Imp Len time is up. Fault reset, performed either by pressing the Fault reset button or through binary
input, has no influence on this output.
12.3.24 BakTrpPer
Backup trip permanent relay; closes if any of the
or
is
activated and CB Feedback doesn't deactivate within Bak Trp Del. Resets by successful fault reset or if the CB
Feedback deactivates before the countdown stops.
If the CB Feedback input or Bak Trp output are not configured on any physical input or output, this function is
blocked.
12.3.25 !BakTrpPer
Inverse backup trip permanent relay; opens if any of the
or
is activated and CB Feedback doesn't deactivate within BakTrpPer (page 1). Resets by successful fault reset
or if the CB Feedback deactivates before the countdown stops.
If the CB Feedback input or Bak Trp output are not configured on any physical input or output, this function is
blocked.