12.2 Library of Binary switches
12.2.1 Ext Trip
Activation of this input causes immediate trip of the protection. The trip conditions are active throughout the
activation of this input.
12.2.2 Fault Reset
Activation of this switch causes fault reset. The input has the same effect as pushing the button FltRes. If
permanently activated, every 100ms an impulse to fault reset the unit is done internally.
12.2.3 Alt Settings
Activation of this switch causes immediate switching to the setting, done in the setpoint groups marked as
„A.xx”. In case that the switchover comes in the moment when a delay of some of the protection stage is being
count-down (the unit is about to trip), the timer setting is kept as before the switch. However, if the trip
conditions change during the delay run (e.g. by changing the protection threshold), the trip is not performed.
12.2.4 Disable
Activation of this switch disables immediately all protective features of the unit. The switch may be used e.g. in
case that the generator is not yet in parallel-to-mains operation, and so the mains parameters do not have to be
evaluated. In this case, the unit does not trip on any fault conditions.
12.2.5 CB Feedback
Deactivation of this switch confirms opening of the circuit breaker after a trip is issued by MainsPro. If the
feedback does not confirm opening of the CB, additional back-up trip BakTrpPer or BakTrpImp will be issued
after adjustable time delay BakTrp Del.