InteliVision 18Touch 1.0 Global Guide
26
Image 6.7 Controller IP settings
Note:
IP addresses of the controllers must be accessible from the IV18T. If the IV18T is connected to another
LAN segment than the gen-sets are, there must be a gateway (router) that enables direct traffic between the
segments. If the IV18T is connected via the Internet, then the internet gateway of the LAN where gen-sets are
connected must have public IP address, must allow incoming traffic and must provide port forwarding from the
external public IP to the various internal gen-set IPs according to the port used.
Image 6.8 Internet gateway (router) configuration example
6.2.3 Ethernet (Internet) connection via InternetBridge-NT
Up to 32 controllers can be remotely monitored via a single InternetBridge-NT. The response time of a system
with this type of connection depends on the number of controllers. The higher the number of controllers, the
slower the system response time. It is also possible to interconnect IV18T and controllers locally via
InternetBridge-NT as a local bridge from the Ethernet network to the CAN fieldbus or RS-485 interface.