Conformity declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
!! Warnings !!
Be aware that the binary outputs can change state during and after software
reprogramming (before the controller is used again ensure that the proper
configuration and setpoint settings are set in the controller)!!!
Be aware that gen-set can automatically or remotely start when following
controller terminals are disconnected !!!
•
Mains voltage measuring and / or
•
Binary outputs for MCB control and / or
•
MCB
feedback
Switch
InteliGen
NT
to OFF mode and disconnect the Binary outputs Starter and Fuel to
avoid unexpected automatic start of gen-set and GCB closing
.
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to
update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly
undertaken.
!!! CAUTION !!!
Dangerous voltage
In no case touch the terminals for voltage and current measurement!
Always properly connect grounding terminals!
Take care when disconnecting In/Im3 terminals when the gen-set is stopped.
For safety connect parallel to controller In/Im3 terminals two anti parallel diodes 10A/100V.
In any case do not disconnect generator CT terminals when the gen-set is loaded.
Adjust set points
All setpoints are preadjusted to their typical values. But the setpoints in the “
Basic settings
”
settings group
!!must!!
be adjusted before the first startup of the gen-set.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
CAN DESTROY THE GEN-SET !!!
The following instructions are for qualified personnel only.
To avoid personal injury do not perform any action not specified in this User guide !!!