InteliSys
NT
-AFR-Abstract, SW version 1.0, ©ComAp – December 2006 30
IS-NT-AFR-1.0-Abstract.pdf
Engine shut down protection is activated when no GasVTest feedback is detected during
GasVTest
del
.
Step:
1
s
Range:
0 to 300 s
Gas valve
test unit
IS-CU
BinaryOutput
GasVTest run
BinaryInput
GasVTest OK
BO GasVTest run
Starter
BI GasVTest OK
Start
command
GasVTest del
opened
opened
Engine
shut down
BO GasVTest run
Prestart
BI GasVTest OK
OK
Start
command
GasVTest del
Engine start
…. Starting procedure
StartPosition [
%
]
Mixer fix position for Engine start when Binary input GasSelection is opened.
Step:
0,1 %
Range:
0,0 to 100,0 %
RunPosition [
%
]
Mixer fix position after engine reaches Nominal RPM when GCB is opened. Position is active when
Binary input GasSelection is opened.
Step:
0,1 %
Range:
0,0 to 100,0 %
LoPwrPosition
[
%
]
Mixer low power fix position after GCB is closed until gen-set reaches
Low MAP power
. Position is
active when Binary input GasSelection is opened.
Step:
0,1 %
Range:
0,0 to 100,0 %
Hint:
Use Force value function to force different value of StartPosition, RunPosition and LoPwrPosition.
MxPos40%CH4, MxPos60%CH4
[ % ]
Setpoints for transformation from CH4 content to Mixer position output. This function is active when
Ana CH4 = ENABLED.
Step:
0,1 %
Range:
0,0 to 100,0 %
4 - 20 mA
A
na C
H
4
% CH4
Ana CH4
Mi
x p
os
C
H
4
%
40%
60%
MxPos60%CH4
MxPos40%CH4
Example:
Setting MxPos40%CH4 = 40% and MxPos6%CH4 = 60% means linear 1:1 transformation between
CH4 and Mixer position.