5.4.23 Alternate configuration
5.4.1 Start-stop sequence
State
Condition of the transition
Action
Next state
Ready
Start request
on
counter started
Prestart
RPM > 2 or Oil pressure >
or Generator
voltage > 10V or D+ voltage is
higher than 80%
Stop (Stop
fail)
OFF Mode selected or Shutdown
alarm active
Not Ready
Not Ready
RPM < 2, Oil pressure not
detected, Generator voltage < 10V,
D+ not Active no shutdown alarm
active, other than OFF Mode
selected
Ready
Prestart
Prestart time elapsed
on,
on,
counter
started
Cranking
Cranking
RPM > Starting RPM
off,
off
Starting
D+ input activated or oil pressure
detected or Generator voltage >
25% Nominal voltage
off,
off
Cranking
, 1st attempt
off,
off,
on,
timer started
Crank
pause
Maximum Cranking Time (page 165)
elapsed, last attempt
off,
off
Shutdown
(Start fail)
Crank pause
Cranking Fail Pause (page 165)
elapsed
on,
on,
off,
counter
started
Cranking
Starting
elapsed
Minimal Stabilization Time (page 171)
and
Maximal Stabilization Time (page
counter started
Running
any shutdown condition
off,
Shutdown
Содержание InteliLite MRS16
Страница 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Страница 55: ...InteliLite Global Guide 55 ...
Страница 56: ...InteliLite Global Guide 56 ...
Страница 57: ...InteliLite Global Guide 57 ...
Страница 58: ...InteliLite Global Guide 58 ...
Страница 59: ...InteliLite Global Guide 59 ...
Страница 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Страница 61: ...InteliLite Global Guide 61 History Log ...
Страница 62: ...InteliLite Global Guide 62 ...
Страница 63: ...InteliLite Global Guide 63 ...
Страница 64: ...InteliLite Global Guide 64 ...
Страница 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Страница 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Страница 67: ...InteliLite Global Guide 67 Change password ...
Страница 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Страница 69: ...InteliLite Global Guide 69 Log out from controller ...
Страница 70: ...InteliLite Global Guide 70 Note Enter invalid password to log out from controller 5 3 5 Information screen ...
Страница 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Страница 72: ...InteliLite Global Guide 72 ...
Страница 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Страница 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Страница 102: ...InteliLite Global Guide 102 5 4 15 Flowchart Image 5 30 Basic flowchart of controller sequences ...
Страница 170: ...InteliLite Global Guide 170 Image 8 5 Idle Time 1 Image 8 6 Idle Time 2 6 back to List of setpoints ...
Страница 550: ...InteliLite Global Guide 550 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...
Страница 617: ...InteliLite Global Guide 617 Image 9 29 I LB Image 9 30 I LB dimensions Note All dimensions are in mm ...