5.5.18 Gen-set operation states
Engine state machine
Init
Autotest during controller power on.
Note:
Sometimes controller stays in Init mode after FW upgrade. It means that there are
new parameters which should be checked by user. It is possible to disable this control
via InteliConfig.
Not ready
Gen-set is not ready to start.
Example:
When shutdown alarm is active or unit is in OFF mode.
Prestart
Prestart sequence in process,
output is closed.
Example:
Usually used for preheating or processes executed prior gen-set start.
Cranking
Engine is cranking,
output is closed
Pause
Pause between start attempts.
Starting
Starting speed is reached and the Idle timer is running.
Running
Gen-set is running at nominal speed.
Loaded
Gen-set is running at nominal speed and
is closed.
Stop
Stop.
Example:
Automatic or manual stop command was issued, engine is stopping.
Shutdown
Shut-down alarm activated.
Ready
Gen-set is ready to run.
Cooling
Gen-set is cooling before stop.
EmergMan
gen-set operation.
Example:
Used for bypass the controller and engine manual start.
Engine started conditions
Engine speed (RPM) >
or
Oil pressure >
Starting Oil Pressure (page 192)
or
Binary input
is in logical 0 or
D+ terminal active (reached
of supply voltage) for minimum 1 s or
Generator voltage > 25% of
Nominal Voltage Ph-N (page 179)
or
Nominal Voltage Ph-Ph (page 179)
(any phase)
Note:
Any of these condition will disconnect starter of the engine, however for transition to next state RPM
needs to be higher than
.
Engine running conditions
Engine speed (RPM) >
or
Oil pressure >
Starting Oil Pressure (page 192)
or
Binary input
is in logical 0 or
Generator voltage > 25% of
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...