InteliLite Global Guide
527
LBI: E
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
951
Description
This binary input is used to switch on
, when engine start is not requested. It
is intended to enable engine values reading, when engine doesn't run.
When this binary input is active, binary output
is active too.
When this binary input is inactive, function of
is not affected.
ECU Key Switch
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
164
Description
This binary input is used to set the setpoint
ECU Speed Adjustment (page 226)
by binary inputs. When the
LBI is activated the setpoint is decreased by 2%.
ECU Speed Down
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
165
Description
This binary input is used to set the setpoint
ECU Speed Adjustment (page 226)
by binary inputs. When the
LBI is activated the setpoint is increase by 2%.
ECU Speed Up
back to Logical binary inputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
45
Description
This input is designed to allow the gen-set or breakers to be controlled externally, not by the controller. This
feature can be useful in case of some failure, which disables the gen-set or breakers to be controlled by the
controller, but the gen-set itself is operational.
The controller behaves in the following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the gen-set or breaker control, deactivates all outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not activated if nonzero speed is detected.
When the input is deactivated, the controller takes control according to the situation in the moment of
deactivation, i.e. the gen-set remains running loaded if it was running and GCB was closed in the
moment the input was deactivated.
Emergency MAN
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...