InteliLite 9 Global Guide
381
Alarm Type
Shutdown
Alarmlist message
Sd RPM Measurement Fail
Alarm evaluated
During cranking
Related applications
AMF, MRS
Description
The alarm is issued if the engine speed has not exceeded the
within the
Maximum Cranking Time (page 160)
, although some of additional
running engine indication sources indicate that the engine has started.
Sd RPM Measurement Fail
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Short Circuit
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
adjusts the short current limit
Short Circuit BOC Delay (page 193)
adjusts the delay in fine steps
Sd Short Circuit
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Start Fail
Alarm evaluated
When the gen-set is being started
Related applications
AMF, MRS
Description
This alarm will be issued after all attempts to start the gen-set have run out but the
gen-set did not start. The following setpoints are related to this alarm:
adjust the number of attempts
Sd Start Fail
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Underspeed
Alarm evaluated
Engine running only
Related applications
AMF, MRS
Description
This alarm will be issued when the gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint
The underspeed alarm starts to be evaluated after successful gen-set start and is
being evaluated for the entire time that the fuel solenoid is on.
Sd Underspeed
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...