InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
291
T
IMING OF BREAKER CONTROL OUTPUTS
15.2.1.2
Binary output: BTB ON Coil
Related FW
3.0
Description
This output is intended for closing of the BTB using ON coil if a
circuit
breaker
is used as BTB. The output provides 2 sec pulse when the BTB has
to close. If synchronizing is disabled with the particular breaker, the pulse
length is extended to 5sec. See timing diagram of all available breaker
control outputs in the description of the
BTB close/open
output.
There are also other outputs availabe for BTB control:
BTB close/open
15.2.1.3
Binary output: BTB OFF Coil
Related FW
3.0
Description
This output is intended for opening of the BTB using OFF coil if a
circuit
breaker
is used as BTB. The output provides 2 sec pulse when the BTB has
to open. If synchronizing is disabled with the particular breaker, the pulse
length is extended to 5sec. See timing diagram of all available breaker