InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
227
Units
kW
Related FW
3.0
Description
This value shows the sum of nominal powers of all gensets that are available
for power management (in any state - stopped, running etc.). See also values
TotRunPnomAll
and
. This value is active only when BTB is
closed.
For more information on power management please refer to the chapter
Power management
.
13.1.5.2
Value: TotRunPnom
Group
Pwr management
Units
kW
Related FW
3.0
Description
This value shows the sum of nominal powers of all running gensets that are
participating in power management. See also values
TotRunPnomAll
and
. This value is active only when BTB is closed.
For more information on power management please refer to the chapter
Power management
.
13.1.5.3
Value: Act Reserve
Group
Pwr management
Units
-
Related FW
3.0
Description
Actual
absolute reserve
. This value is active only when BTB is closed. In BTB,
it can be used in
two-level load shedding
.
13.1.5.4
Value: LoadRes Start
Group
Pwr management
Units
kX
Related FW
3.0
Description
If the actual absolute reserve is lower than this value the next gen-set which
is about to be started in
power managament
is started. This value is the
exact copy of setpoint
#LoadResStrt X
.
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...