![ComAp IA-NT Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/comap/ia-nt/ia-nt_manual_2638905053.webp)
Accessory Modules for IL-NT, IC-NT, IA-NT and ID-Lite Global Guide
53
Setpoint group
LiteEdit configuration
Range [units]
0 - PeakLevelStart [kW]
Default value
Force value
Alternative config
YES
Step
0.1 or 1
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Load consumption level the gen-set has to stop at. Genset stop is PeakAutS/Sdel delayed after
PeakLevelStop limit is reached. Load consumption is calculated (not directly measured) as a sum of gen-
set and mains active power.
PeakLevelStop [kW]
Setpoint group
LiteEdit configuration
Range [units]
0 (OFF) - 600 [s]
Default value
0
Force value
Alternative config
YES
Step
1 [s]
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
The condition for the "peak" automatic start or stop must be valid for time period longer than value of this
setpoint to execute the automatic start or stop. Adjusting 0 causes stop of the gen-set (if there is no other
demand for running) and disable the automatic start.
PeakAutS/S Del [s]
Setpoint group
LiteEdit configuration
Range [units]
DISABLED / ENABLED [-]
Default value
Force value
Alternative config
YES
Step
-
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Tells controller to activate protection against power export to the mains. The function limits gen-set
requested power to hold import power higher or equal to the setpoint Export kW. DISABLED / ENABLED
Export Limit [-]