Accessory Modules for IL-NT, IC-NT, IA-NT and ID-Lite Global Guide
52
Setpoint group
LiteEdit configuration
Range [units]
1 – 5000 [A/5A]
Default value
1
Force value
Alternative config
YES
Step
1
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
This setpoint defines mains current transformer ratio for current measuring input of IC-NT-CT-BIO7
module.
Im CT Ratiol [A/5A]
Setpoint group
LiteEdit configuration
Range [units]
PeakLevelStop – 3200 [kW]
Default value
Force value
Alternative config
YES
Step
0.1 or 1
Comm object
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Load consumption level the gen-set has to start at. Function is inactive when PeakAutS/Sdel = OFF.
Genset start is PeakAutS/S Del delayed after the consumption of the Load exceeds the PeakLevelStart
limit.
PeakLevelStart [kW]