COLUMBIA BOILER COMPANY, REV 2-17
- 20 -
Adjust the main scale set point about 20 PSI higher than the operating pressure control by
turning the main scale adjusting screw on top of the case until the main scale setting indi-
cator is at the desired pressure.
There are a number of pressure controls that may be used interchangeably. Please see
additional information in the manual appendices.
Safety Valve
Safety valves shall be piped so that any discharge cannot cause injury to people or dam-
age to property. The discharge piping must be supported so that the weight of the piping
is not transmitted to the safety valve body. The weight supported by the valve outlet should
not exceed that of a drip pan elbow. Installations requiring long discharge piping should
not be connected directly to the safety valve. Refer to Drawing PL-049 in the Appendix.
In order to achieve the topmost performance and maximum safety valve life, maintain a
proper operating gap between the set pressure of the safety valve and the maximum oper-
ating pressure of the boiler.
The minimum recommended operating gap for this valve is 10%, but at no time less than
7 PSI. Under no circumstances should this gap be less than 7 PSI or seat leakage can
occur. Failure to maintain this operating gap can result in an accumulation of deposits on
the seating surface that may impede proper operation of the safety valve.
If the valve discharges on its own, contact a qualified service technician to determine the
cause. This may be an indication of equipment or system malfunction.
Gauge Glass Protector
The gauge glass protector is provided to guard against personnel injury and component
damage in the event of a breakage of the sight glass. The gauge glass protector must be
properly installed prior to operation of the boiler.
DESCRIPTION OF OPTIONAL EQUIPMENT
Manual Dual Pressure
(Optional)
A toggle switch is provided in conjunction with an additional Pressuretrol to manually
change from a high operating pressure to a low operating pressure. See wiring diagrams
enclosed.
Manual Reset Pushbutton (After Low Water Cut off)
(Optional)
A normally closed, Manual Reset Pushbutton and Control Board is available. This pushbut-
ton, when installed, must be pressed and held for 10 seconds to start burner operation
after a low water condition has been corrected.
Содержание CT-10
Страница 14: ... COLUMBIA BOILER COMPANY REV 2 17 11 Figure 4 BLOWDOWN PIPING ...
Страница 31: ... COLUMBIA BOILER COMPANY REV 2 17 28 MAINTENANCE LOG ...
Страница 32: ... COLUMBIA BOILER COMPANY REV 2 17 29 MAINTENANCE LOG ...
Страница 43: ...APPENDICES ...
Страница 44: ......
Страница 48: ......
Страница 49: ......
Страница 51: ......
Страница 52: ......
Страница 54: ......
Страница 55: ......