RECOMMENDED
ANALYSIS COMMENTS
RANGE
pH 10-11 Low pH promotes corrosion
Total Alkalinity 200-700 ppm Low promotes corrosion
Phosphates 30-100 ppm Prevent scale formation
Total Hardness 0-50 ppm Prevents scale formation
Chlorides 60-200 ppm A measure of proper blow down
Total Dissolved Solids 2000 ppm Maximum High solids may cause surging
Sulfites 20-30 ppm A good oxygen scavenger
Specific Conductance < 700 micro ohms cm A measure of proper blowdown
Oxygen < .007 mg/liter Prevents corrosion and pitting
ppm = parts per million
Recommended Guidelines for Boiler Water Treatment
WARNING
Have your water tested by a local waer treatment specialist!
Proper Water Chemistry is essential to prevent scale, or other deposits, and corrosion with-
in the boiler. The absence of adequate external and internal treatments can lead to oper-
ational upsets or total boiler failure that is not covered under warranty.