3
1.
Installation must conform to requirements of authority
having jurisdiction or, in absence of such requirements,
to the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or Natural Gas and Propane Installation Code,
CAN/BS149.1
2.
Where required by the authority having jurisdiction,
installation must conform to Standard for Controls and
Safety Devices for Automatically Fired Boilers, ANSI/
ASME No. CSD-1.
3.
This boiler is classified as Category I and III and vent
installation shall be in accordance with latest revision of
the National Fuel Gas Code, ANSI Z223.1 or applicable
provisions of the local building codes.
4.
LOCATE BOILER on level, solid base as near outside
wall as possible and centrally located with respect to
heat distribution system as practicable.
5.
Allow 24 inches at front and right side for servicing and
cleaning.
6.
When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to
permit replacement of another appliance such as a
water heater.
7.
Install boiler such that gas ignition system components
are protected from water, (dripping, spraying,
rain, etc.), during appliance operation and service,
(circulator replacement, condensate trap, control
replacement, etc.).
8.
Requirements for Commonwealth of
Massachusetts: Boiler installation must conform to
Commonwealth of Massachusetts code 248 CMR which
includes but is not limited to installation by licensed
plumber or gas fitter.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY. *Boiler must NOT be installed on
carpeting.
10.
Minimum clearances to combustible constructions are:
TOP ...........................................18 in. (457mm)
FRONT ........................................6 in (152mm)
FLUE CONNECTOR .........................6 in (152mm)
REAR............................................4 in. (102mm)
CONTROL SIDE..............................9 in. (229mm)
OTHER SIDE .................................3 in. (76mm)
VENT PIPE ....................................6 in.
(152mm)
INTRODUCTION
!
WARNING
1. Keep boiler area clear and free from
combustible materials, gasoline and other
flammable vapors and liquids.
2. DO NOT obstruct air openings to boiler
room.
3. Modification, substitution or elimination
of factory equipped, supplied or specified
components may result in property damage,
personal injury or loss of life.
4. To
owner: Installation and service of this
boiler must be performed by qualified installer.
5. To i
nstaller: Leave all instructions with
boiler for future reference.
6.
Boiler installation must conform to
Commonwealth of Massachusetts code 248
CMR when installed in Commonwealth of
Massachusettes. This includes, but is not
limited to, installation by licensed plumber or
gas fitter.
!
WARNING
Improper installation, adjustment, alteration,
service or maintenance can cause injury or
property damage.
NOTICE
• Greater clearances for access should
supersede fire protection clearances.
* For installation on combustible flooring
Special Base MUST BE USED. (See
Replacement Parts Section)
Содержание CDVB-100
Страница 15: ...15 HORIZONTAL VENT INSTALLATION INSTRUCTIONS Figure 9 Figure 7a Vent Cap Figure 7b Figure 8 ...
Страница 22: ...22 HORIZONTAL VENT INSTALLATION INSTRUCTIONS Figure 16 Termination Clearances ...
Страница 31: ...31 PILOT PILOT ELECTRICAL WIRING Figure 26 HOT WATER CONTROL AND INTERMITTENT IGNITION WIRING ...
Страница 44: ...Columbia Company Main offices and factory Pottstown PA ...