MOUNTING AND ALIGNMENT OF FIXTURE
1.
Mount and secure each fixture into the designated position in accordance to the installation plan. Ensure there is
sufficient cable length between the fixture and junction box to allow for final alignment of the fixture.
2.
Secure the fixtures to a solid mounting surface using three threaded fasteners minimum of 3/8 inch (10mm) stainless
steel complete with flat and locking washer.
3.
Rotate/tilt the fixture into the desired position.
4-PIN INTERFACE
Pin 1 Pin 4
Pin 1
+
Line Voltage
Pin 2
-
Neutral
Pin 3
Shield
Ground
Pin 4
Reserved Leave Open
REQUIRES ELECTRICIAN TO INSTALL
NOTE: Supply lead wires should not be connected to a dimmer of any sort.
DATA CONNECTION
•
Inline DMX amplifier required if run length exceeds: 125 feet between fixtures (others)
•
Maximum run length from DMX controller to last fixture: 1000 feet
•
DMX must be continuous from controller to last fixture in a run. A splitter is needed if signal is split
•
If provided data cables won’t be used, please note that any cables must meet EIA-RS485 requirements and warranty may
be voided
•
To comply with all local codes and jurisdiction, qualified communications technicians must do communications wiring
•
To avoid signal transmission problems and interference, it is always advisable to connect to a DMX signal terminator
•
Communication cables and AC power lines must not be run in the same conduit
o
Route Data Cables in series between fixture and any communications accessories using DATA IN and DATA OUT
o
To ensure they are easily accessed once construction is complete, secure data cables near the fixtures
800.595.6302 coloronix.com
|
1
1
ColorFlood Square
C-SS2-RGBW-10S-24
DMX IN
DMX
DMX
DMX
PWR
PWR
PWR
PWR IN
To DMX SOURCE
USE DMX SIGNAL REPEATER ON EVERY 32nd SS2 UNIT IN A CHAIN
OR WHEN A DATA CABLE RUN BETWEEN UNITS EXCEEDS 100'.
DMX = C-SWR-DMX-WL-80 or 300 PWR = C-SWR-PWR-WL-80