7
Outdoor Siren 24V (CAE24V)
Features:
•
Power supply tension from 24 to 30Vdc (with polarity).
•
Current consumption: 1.5 A
•
Maximum sonorous level: 116 dB
•
2-wires basic connection
•
Wire section 2.5 mm2
•
Size: 185 x 230 x 85
1.4.4.- Repeaters
LONDON control panel enable to connect up to 10 repeaters , trough 4-wire connection (2 of power
supply and 2 of RS 485 communication)
Repeaters show all the information about: alarms, released relays and fault. Also, it is possible to put in order all
the trouble.
1.4.5.- Sub panels
LONDON control panel allows to connect several sub panels. One sub panel is a box with zones and relays
cards. Sub panels has communication with the main control panel trough a RS485 bus communication, with a
maximal distance of 1,2 km. Installation between main control panel and different sub panels is made with 6
cables: 2 for communications RS485, 1 for +5 volts power supply, 1 for +24 volts power supply, 1 for masse and 1
for reset.
The main propose with a sub panels system is simplify the installation with a decrement of cables and costs
times.
1.5.- Accessories.
1.5.1.- PC keyboard
LONDON control panel enable to connect a PC standard keyboard trough Ps2 connector, making the
programming and labelling of zones easier.
1.5.2.- Software de configuración mediante PC.
LONDON conventional control panel has its own software: EasyLondon. This software allows the user to
program the control panel in an easy and intuitive way. Also, information about configuration will be storages for
future uses .
•
PC minimum requirements:
•
Pentium II
•
32 Megas of RAM
•
50 Megas of free space in Hard Disk
•
CD-ROM
1.5.3.- Printer
System allows to connect a printer in order to print all trouble indicating date and hour when trouble has
happened.
Printer configuration (see printer manufacturer specification) has to coincide with following field registered
in control panel:
Band Rate
Nº bits
Parity
Stop bits