8. CONFIGURATION.
Values may be changed by using
p
q
, changes can be saved by pressing
ENTER
. If you wish to quit the configuration sequence,
press
MENU
. Each time
ENTER
is pressed, the different screens, which display the sequence of configuration, will open
automatically.
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
3”
3”
E
N
EN
Push
MENU
for 3 seconds
.
to start configuration sequence
This temporary message gives information about the software version
Choose language using the
ENGLISH”, “LANGUE FRANÇAISE”, “LINGUA ITALIANA” and “IDIOMA ESPAÑOL”.
p
q
keys: PRACHE DEUTSCHE”, “LANGUAGE
If there is no external device for detecting the minimum water level, press
ENTER
to
confirm. Otherwise, change NO for YES using the
p
q
keys.
In this step, the mode of operation can be selected using
p
q
. There are 2 options:
n
On-off mode: only the start pressure is configured. The pump will start at this
pressure - with the delay configured in the next step - and it will stop when there is
no flow demand.
n
Pressure-dependent mode: the start and stop pressures of the pump can be
configured.
The
rated current intensity - from 0 to 10 A - is entered by means of the
p
q
keys to
enable thermal protection of the motor. This value is given on the name plate of the
motor. Press
ENTER
to confirm.
This is the start pressure for the pump. The desired pressure values within the respective
range can be chosen using the
p
q
keys:
n
On-off mode: from 1 to 5 bars.
n
Pressure-dependent mode: from 0 to 6,5 bar.
This is the stop pressure for the pump in pressure-dependent mode. It must be within a
range of
1 to 7 bar and 1 bar above the start pressure.
Use
p
q
to modify the values.
This is the delay to start the pump once it has reached the start pressure. Choose the
desired timing using the
p
q
keys.
This is the delay to stop the pump once it has reached the stop pressure. Choose the
desired timing using the
p
q
keys.
System is ready to operate.
Press
AUTOMATIC On/Off
, green LED is lit.
From this moment the LCD screen will show:
n
On-off mode: current pressure (PLINE) and start pressure (PON).
n
Pressure-dependent mode: current pressure (PLINE), start pressure (PON) and
stop pressure (POFF).
Using
p
in
AUTOMATIC
mode, it is possible to access a detailed expert screen with the
following parameters:
n
P line: current pressure.
n
INT: present current consumption.
n
F: position of the flow sensor (0: no flow, 1: with flow)
0
1
2
3
4
(1)
5
(2)
6
7
8
9
10
INT. MAX.
LEVEL PROBE
NOT
OPERATING MODE
ON-OFF
OPERATING MODE
PRESSOSTATIC
PLINE PON
05,0 03,0
PLINE INT F
05,0 9,0 1
START DELAY
00 sec
STOP DELAY
00 sec
P ON
05,0 bar
PLINE PON POFF
05,0 02,0 06,0
P OFF
06,0 bar
PLINE PON
03,0 bar 02,0 bar
LANGUAGE
ENGLISH
ONEMATIC
V 0.0
OFF
7. STARTUP.
n
It is recommended to connect
ONEMATIC
to the electric supply via the motor protection switch. Wait for 5 seconds while the
ONEMATIC
is
running autotest.
n
If the unit is started for the first time, it will directly open the configuration menu. The LCD screen will display a message for language selection.
Choose your language and start the configuration procedure - see
7. CONFIGURATION
.
n
Once the unit is configured, switch to manual mode by pressing the
AUTO On/Off
push-button (green LED off). Verify the rotational direction
of the pump, and whether it is correctly primed using the
Start/Stop
push-button.
n
Press
AUTO On/off
. The unit is ready to operate.
5
On
Off
(1) “
P ON”
must be at least 0.2 bar higher than manometric pressure.
Eg: with 20 meters of water column
ð
P ON
> 2.2 bar.
The pump must be able to supply at least 0.5 bar more than “
P ON
”.
(2) Being in pressure dependent mode “
P OFF
” must be at least 0.5 bar lower than the pressure supplied by the pump.
Содержание Onematic
Страница 23: ......
Страница 24: ...130502D_v10...