PowerTALK 101
39
Testing procedure
It is suggested that a PowerTALK unit or system is laboratory tested prior to shipping to site.
A simple, but effective test is described below:
Using the default settings on the PowerTALK unit, i.e.: 9600 8N1, with the standard IP addresses,
as are indicated on the back of the units.
1.
Power
up
2
PowerTALK
units,
confirming that the green “ON” LEDs
are on
2.
Connect a Server Flylead (Crossed
over UTP lead) between the
two
PowerTALK units
3.
Connect a loopback connector to port 1
or 2 on a PowerTALK 101 unit
4.
Connect a Laplink cable between the
other PowerTALK unit, and the PC
COM2.
5.
Run HyperTerminal on Windows 95/NT
6.
Set HyperTerminal to COMn where
COMn is your available COM port
7.
Set
HyperTerminal
to
the
settings
shown on the right
8.
Ensure
“local
echo”
is
off
on
HyperTerminal
9.
Type
into
the
terminal
emulation
program, and you should see an echo
returning on the screen. This comes
from the loopback plug, and will stop if
the loopback plug is removed.
10.
The LED indications can also carefully
be checked, observing the flow of data.
Содержание PowerTALK 101
Страница 1: ......
Страница 2: ...User s Manual PowerTALK 101 Ethernet to Serial converter ...
Страница 7: ...PowerTALK 101 6 ...
Страница 25: ...PowerTALK 101 24 ...
Страница 54: ...PowerTALK 101 53 Notes ...
Страница 55: ...PowerTALK 101 54 ...