Connecting Cables (not included)

Power wire and wiring are very important to the
performance of the inverter. Because the inverter has a
low voltage, high current input, low resistance wiring is
essential between the battery and inverter. This is so it 
can deliver the maximum amount of energy to the load. 

Use only copper wire. Aluminum wire has about one-third
more resistance than copper wire of the same size, plus it
is difficult to make good, low-resistance connections to
aluminum wire.

We recommend #4 AWG copper cable (90°C insulation
rating) as the minimum size for connections between
the battery and inverter.

Keep the cable length as short as possible, no more
than four feet (one and a half meters). This will keep the
voltage drop to a minimum.

If the cable has too much voltage drop, the inverter may
shut down when drawing higher currents because voltage
at the inverter may drop below 10 volts. If you must use
longer cables, choose thicker cables, such as #2 AWG,
and trim the ends of the cable to fit the terminals.

To connect the cables between the 
inverter and the battery:

1. Press the Power Button on the inverter to the off

position. If the power source is a DC power supply,
switch it off as well.

2. On the end of the cable that connects to the inverter,

strip back the insulation about one-half inch (one and
one-half cm), exposing the bare copper conductor.

3. Connect cable to the Power Input Terminals on input

end of the inverter. The red terminal is positive (+) and
the black terminal is negative (-). Insert the bare ends
of the cables into the terminals and tighten the screws
to clamp the wires securely. 

It is a good idea to check and tighten these screws
from time to time. They can become loose by
vibrations or thermal cycling.

4. Connect cables to the power source:

a. Connect the cable from the Negative (Black)

Terminal of inverter to the Negative Terminal
of the power source. Make a secure connection.

Connecting Cables

Connecting Cables

Intro

Operation

Customer
Assistance

Warranty

Notes

Notice

Secondary Icons

Caution

Warning

Installation

Installation

Intro

Operation

Customer
Assistance

Warranty

Notes

Notice

Secondary Icons

Caution

Warning

Installation

Installation

Insert Bare Cables

Power Button

Intro

Operation

Customer
Assistance

Warranty

Notes

Notice

Main Icons

Secondary Icons

Caution

Warning

Installation

Strip the Insulation

10275_CPI1575_PH3  8/14/07  8:38 AM  Page 8

Содержание CPI 1575

Страница 1: ...further assistance after reading this manual Cobra Electronics offers the following customer assistance services For Assistance in the U S A Automated Help Desk English only 24 hours a day 7 days a we...

Страница 2: ...Thanks to You A1 Customer Assistance A1 Product Features A2 Important Safety Information 1 Quick Evaluation Before Installation 4 Installation Installation Requirements 6 Mounting 7 Connecting Cables...

Страница 3: ...tements in the manual CAUTION Statements specify conditions which could cause damage to the unit or other equipment WARNING Statements identify conditions that could result in personal injury or loss...

Страница 4: ...ery chargers for battery packs used in hand power tools These chargers have a WARNING label stating that dangerous voltages are present at the battery terminals This problem does not occur with the va...

Страница 5: ...ce connection For example if the power source is a battery the cable must be terminated with a battery terminal that clamps to the post on the battery Power Source A test load that can be plugged into...

Страница 6: ...lt CAUTION The inverter must only be connected to batteries with a nominal output voltage of 12 volts It will not work with a 6 volt battery and will be damaged if it is connected to a 16 volt battery...

Страница 7: ...ry 1 Press the Power Button on the inverter to the off position If the power source is a DC power supply switch it off as well 2 On the end of the cable that connects to the inverter strip back the in...

Страница 8: ...result Thoroughly ventilate the battery compartment before making this connection b Connect the cable from the Positive Red Terminal of the inverter to the Positive Terminal of the power source the ba...

Страница 9: ...ed running time in hours Power x Operating Time Watt Hours 4 Divide the watt hours by 10 to determine how many battery 12 volt ampere hours will be consumed Ground Wiring There is a screw on the rear...

Страница 10: ...amperes from the battery This is low current draw It would take more than a week to discharge a 100 ampere hour battery at this rate depending on the age of the battery Remote On Off Switch An optiona...

Страница 11: ...utput of the inverter is short circuited for one second or more it will shut down to protect itself The meter will flash as shown to indicate Short Circuit Protect and an alarm will sound To restore n...

Страница 12: ...over discharged It will restart when the input voltage exceeds 12V 0 3V The inverter will also shut down if the input voltage exceeds 15 5V 0 5V This protects the inverter against excessive input vol...

Страница 13: ...es as the load increases The unit is completely insulated in input and output for added safety Troubleshooting Guide Intro Operation Customer Assistance Warranty Notes Notice Main Icons Secondary Icon...

Страница 14: ...rning Installation Customer Assistance Limited Two Year Warranty For Products Purchased in the U S A Cobra Electronics Corporation warrants that its Cobra power inverter and the component parts thereo...

Страница 15: ...om the main menu 8 00 a m to 6 00 p m CT Monday through Friday Make check or money order payable to Cobra Electronics Attn Accessories Dept 6500 West Cortland Street Chicago IL 60707 USA To order onli...

Отзывы: