Service manual
- 34 -
9.8.5 Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
T
T temp. up
T temp. down
TE2
Setting fan speed
Fan off
Breeze
TE3
TE1
TE4
9.8.6 Auto wind at heating mode (T=indoor temp.)
0
T-Ts
Room temp. up
Room temp. down
2
Med fan
High fan
9.8.7 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
T
T temp. up
T temp. down
TE7
Compressor on
Fan on
TE8
TE9
Compressor off
Fan off
Compressor on
Fan off
The louver opens to Standard Angle ANGLHEAT when power is on for the first time
9.9 Defrosting mode(available for heating mode)
9.9.1 Defrosting condition:
Defrost starts when either of the following 1&2:
1.
T3 lower than 0’C, lasts for more than 40 minutes,
and during this period T3 is lower than -
3’C
consecutively reaches 3 minutes.
2. Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan