15
27
Floating charging voltage
3.5K default setting: 27.0V
5.5K default setting: 54.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V for 3.5KVA model and
48.0V to 61.0V for 5.5KVA model. Increment of each click is
0.1V.
29
Low DC cut-off voltage
3.5K default setting: 21.0V
5.5K default setting: 42.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 21.0V to 24.0V for 3.5KVA model and
42.0V to 48.0V for 5.5KVA model. Increment of each click is 0.1V.
Low DC cut-off voltage will be fixed to setting value no matter
what percentage of load is connected.
30
Battery equalization
Battery equalization
Battery equalization disable (default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
31
Battery equalization voltage
3.5KVA default setting: 29.2V
5.5KVA default setting: 58.4V
Setting range is from 25.0V to 31.5V for 3.5KVA model and 48.0V
to 61.0V for 5.5KVA model. Increment of each click is 0.1V.
33
Battery equalized time
60min (default)
Setting range is from 5min to 900min.
Increment of each click is 5min.
34
Battery equalized timeout
120min (default)
Setting range is from 5min to 900 min.
Increment of each click is 5 min.