14
16
Charger source priority:
To configure charger
source priority
If this inverter/charger is working in Battery mode, only solar
energy can charge battery.
Solar energy will charge battery if it's
available and sufficient.
18
Alarm control
Alarm on (default)
Alarm off
19
Auto return to default
display screen
Return to default display
screen (default)
If selected, no matter how users
switch display screen, it will
automatically return to default
display screen (Input voltage
/output voltage) after no button is
pressed for 1 minute.
Stay at latest screen
If selected, the display screen will
stay at latest screen user finally
switches.
20
Backlight control
Backlight on (default)
Backlight off
22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable (default)
Bypass enable
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
3.5K default setting: 28.2V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V Increment of each click
is 0.1V.
5.5K default setting: 56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 48.0V to 61.0V Increment of each click
is 0.1V.