
6
Specifications subject to change without notice. 32802000102
REMOTE CONTROL
IMPORTANT: The remote control can operate the unit
from a distance of up to 26 ft. (8 m) as long as there are no
obstructions.When the timer function is used, the remote
control should be kept in the vicinity of the fan coil
(within 26 ft. / 8 m).
The remote control can perform the following basic functions:
• Turn the system
ON
and
OFF
• Select operating mode
• Adjust room air temperature set point and fan speed
• Adjust right-left airflow direction
Refer to the Remote Control Function section for a detailed
description of all the capabilities of the remote control.
Battery Installation
Two AAA 1.5v alkaline batteries (included) are required for
operation of the remote control.
To install or replace batteries:
1. Slide the back cover off the control to open the battery compart-
ment.
2. Insert batteries. Follow the polarity markings inside the battery
compartment.
3. Replace the battery compartment cover.
NOTES:
1. When replacing batteries, do not use old batteries or a different
type battery. This may cause the remote control to malfunction.
2. If the remote is not going to be used for several weeks, remove the
batteries. Otherwise, battery leakage may damage the remote
control.
3. The average battery life under normal use is about 6 months.
4. Replace the batteries when there is no audible beep from the in-
door unit or if the Transmission Indicator fails to light.
5. When batteries are removed, the remote control erases all
programmed settings. The control must be reprogrammed after
insertion of new batteries.
Remote Control Operation - Quick Start
NOTE: When transmitting a command from the remote
control to the unit, be sure to point the control toward the
right side of the unit. The unit confirms receipt of a
command by sounding an audible beep.
1. Turn the unit on by pushing
ON/OFF
.
2. If there is a preference for °C rather than °F (default), press and
hold the
SWING
and
LED/BUZZER
temperature set
point buttons together for approximately 3 seconds.
3. Select the desired mode by pushing
MODE
.
Fig. 4 —Modes
4. Select the temperature set point by pointing the control toward the
unit and pressing the increase/decrease temperature set point
buttons until the desired temperature appears on screen.
5. Select the desired fan speed by pressing
FAN -
or
FAN +
.
NOTE: If the unit is operating in DRY or AUTO mode,
the fan speed will be automatically set.
6. Set the airflow direction. When the unit is turned on, the Up-
Down Airflow louvers default to the cooling or heating position.
The user can adjust the horizontal Up-Down airflow louver
position or have continuous louver movement by pressing
SWING
.
Manual Control
If the remote control is lost, damaged, or the batteries are exhausted,
MANUAL
can be used to run the unit. When
MANUAL
is pressed
once, the
AUTO
mode takes affect (heat or cool). When this button
is pressed twice, the system enters the
TEST
mode and runs for 30
minutes in the
COOLING
mode (it will run in the
AUTO
mode
afterward). When pressed three times, the system turns off.
Fig. 5 —Manual Control Button
The set conditions of manual operation are as follows:
• Preset set point: 76°F (24°C)
• Fan speed:
AUTO
• Discharge air direction: Pre-set position based on
operation in “
Cool
” or “
Heat
” mode.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Handle the control with care and avoid getting the
control wet.
CAUTION
Manual Control Button
Remote Control