22
WSHN-XEE2 10.2-120.2
6.11 Climatic TExt
Function allows the automatic regulation of the preset set-point depending of the outside temperature air measured by the unit probe.
The setpoint defined y the temperature curve is shown at status S0052: ActualUtSetp
Only if P0036: EnCompExt ≠ 0
Path: Main Menu / Unit parameters / TExt Correction confi
Menu accessible only after having entered the password.
Access reserved only to specifically t ained personnel.
The parameter modific tion can cause irreversible damages.
Example
P0612
P0610
P0613
-5
5
10
15
5
10
15
25
30
P0606
P0609
P0607
18
22
24
26
28
30
32
34
2
4
6
8
10
12
14
16
34
0
25
30
20
0
20
T ext.
T ext.
setpoint
setpoint
C o o l i n g
P0608
H e a t i n g
P0611
S0052
S0052
20
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Climatic TExt
6
Climatic TExt (pwd)
Select
Parameter
7
Set
8
Confir
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / TExt Correction confi
Parameters
Short description
Description
P0606
CSptLow
setpoint temperature value when the air temperature value is AirAtSptLowC
P0607
AirAtSetPointLowC
external air temperature value where the calculated setpoint takes on the value given by CSptLow
P0608
CSptHigh
setpoint temperature value when the air temperature value is AirAtSptHigC
P0609
AirAtSetPointHighC
external air temperature value where the calculated setpoint takes on the value given by CSptHigh
P0610
HSptLow
setpoint temperature value when the air temperature value is AirAtSptLowH
P0611
AirAtSptLowH
external air temperature value where the calculated setpoint takes on the value given by HSptLow
P0612
HSptHigh
setpoint temperature value when the air temperature value is AirAtSptHigH
P0613
AirAtSptHigH
external air temperature value where the calculated setpoint takes on the value given by HSptHigh
Содержание WSHN-XEE2 10.2
Страница 7: ...WSHN XEE2 10 2 120 2 7 2 3 Instructions for disassembly Only with options MOBMAG...
Страница 14: ...14 WSHN XEE2 10 2 120 2 5 5 Connections performer by customer dwg n WD8U02400...
Страница 43: ...WSHN XEE2 10 2 120 2 43 9 3 Source side 3 way modulating valve...
Страница 44: ...44 WSHN XEE2 10 2 120 2 9 4 Source side 2 way modulating valve...
Страница 45: ...WSHN XEE2 10 2 120 2 45 9 5 VALVE FOR DOMESTIC HOT WATER...