6.9 Voltages
Check that the air and water temperatures are within in the operating limits.
Start-up the unit.
With unit operating in stable conditions, check:
•
Voltage
•
Total absorption of the unit
•
Absorption of the single electric loads
6.10 Demand limit
Menu accessible only after having entered the password.
Access reserved only to specifically t ained personnel.
The parameter modific tion can cause irreversible damages.
It is possible to limit the absorbed electric power with an external signal 0-10 Vcc.
The higher the signal is, the lower the number of compressors available to meet the thermal need.
If only P0002: EnDemandLimit ≠ 0
Path: Main Menu / Unit parameters / Demand limit
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Set Point
6
Set Point
Select
Demand limit
7
Set
Demand limit
8
Confir
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / Demand limit
Parameters
Short description
Description
P0200
setpointdemandlimit Parameter setting of the value % of demand limit
Содержание WSHN-XEE2 10.2
Страница 7: ...WSHN XEE2 10 2 120 2 7 2 3 Instructions for disassembly Only with options MOBMAG...
Страница 14: ...14 WSHN XEE2 10 2 120 2 5 5 Connections performer by customer dwg n WD8U02400...
Страница 43: ...WSHN XEE2 10 2 120 2 43 9 3 Source side 3 way modulating valve...
Страница 44: ...44 WSHN XEE2 10 2 120 2 9 4 Source side 2 way modulating valve...
Страница 45: ...WSHN XEE2 10 2 120 2 45 9 5 VALVE FOR DOMESTIC HOT WATER...