Parameters
Short description Description
P0002
En DemandLimit Enabling Demand Limit: 0 = disabled, 1 = analogic input, 2 = parameter
P0003
En WaterReset Enabling Water reset: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0050
En 2SetPoint
Enabling 2SetPoint: 0 = Off, 1 = On
P0036
En CompExt
Enabling Climatic TExt: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0051
PrioritaCmd
Status and machine mode priority: Local [0] = Priority to local commands, BMS [1]
priority to commands from plant supervisor
P0053
En DIOn-Off
Enabling remote ON-OFF: 0 = Off, 1 = On
P0090
TypeDL
Inlet signal type: 0 = 0-10V; 1 = 4-20mA
P0091
TypeWR
Inlet signal type: 0 = 0-10V; 1 = 4-20mA
Compressor casing resistances
Connect the compressor oil heating resistances at least 8 hours
before the compressor is to be started:
at the first unit start-up
after each prolonged period of inactivity
1 Power the heaters: isolator switch on 1 / ON.
2 Check the power consumption of the resistances to make sure
that they are functioning.
3 Start-up the compressor only if the crank-case temperature on
the lower side is be higher than the outside temperature by
at least 10°C .
4 Do not start the compressor with the crankcase oil below
operating temperature.
Voltage
Check that the air and water temperatures are within in the
operating limits.
Start-up the unit.
While the unit is operative, i.e. in stable conditions nearing
operating ones, check:
Power supply voltage
Total absorption of the unit
Absorption of the single electric loads
Options
Menu accessible only after having entered the password. Access
reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
Path: Main menu / Unit parameters / Options
6 - START-UP
Содержание WSAT-YSC4
Страница 1: ...R32 M0T400002 01 09 21 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Страница 2: ......
Страница 3: ......
Страница 19: ...Connections performed by costumer 5 ELECTRICAL CONNECTIONS...
Страница 37: ...7 CONTROL...
Страница 39: ...7 CONTROL...
Страница 40: ...7 CONTROL...
Страница 55: ...10 ANTIVIBRATION MOUNTS 1 2 3 4 5 7 6 8...
Страница 57: ...10 ANTIVIBRATION MOUNTS 1 2 3 4 6 7 5...
Страница 76: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...