Compressor casing heater
Check:
closure
Operation
Water side heat exchanger
The exchanger must to be able to provide the maximum thermal
exchange, therefore it is essential for the inner surfaces to be
clean of dirt and build-up.
Periodically check the difference between the temperature of the
supply water and the condensation temperature: if the difference
is greater than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be effected:
with circulation opposite to the usual one
with a speed at least 1,5 times higher than the nominal one
with an appropriate product moderately acid (95% water +
5% phosphoric acid)
after the cleaning rinse with water to inhibit the action of any
residual product
Water filter
Check that no impurities prevent the correct passage of water.
Flow switch
controls the operations
remove incrustations from the palette
Circulation pumps
Check:
no leaks
Bearing status (anomalies are highlighted by abnormal noise
and vibration)
The closing of terminal covers and the correct positioning of
the cable glands.
Insulations
Check the condition of the insulations: if necessary, apply glue
and renew the seals.
Safety valve
The pressure relief valve must be replaced :
if it has intervened
if there is oxidation
based on the date of manufacture, in compliance with local
regulations.
9 - MAINTENANCE
Содержание WSAT-YSC4
Страница 1: ...R32 M0T400002 01 09 21 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Страница 2: ......
Страница 3: ......
Страница 19: ...Connections performed by costumer 5 ELECTRICAL CONNECTIONS...
Страница 37: ...7 CONTROL...
Страница 39: ...7 CONTROL...
Страница 40: ...7 CONTROL...
Страница 55: ...10 ANTIVIBRATION MOUNTS 1 2 3 4 5 7 6 8...
Страница 57: ...10 ANTIVIBRATION MOUNTS 1 2 3 4 6 7 5...
Страница 76: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...