11 Residual risks

General description

In this section the most common situations are indicated,as these 
cannot be controlled by the manufacturer and could be a source of 
risk situations for people or things.
Danger zone
This is an area in which only an authorised operator may work.
The danger zone is the area inside the unit which is accessible only 
with the deliberate removal of protections or parts thereof.

Handling

The handling operations, if implemented without all of the protec-
tion necesssary and without due caution, may cause the drop or the 
tipping of the unit with the consequent damage, even serious, to 
persons, things or the unit itself.
Handle the unit following the instructions provided in the present 
manual regarding the packaging and in compliance with the local 
regulations in force.
Should the refrigerant leak please refer to the refrigerant “Safety 
sheet”.

Installation

The incorrect installation of the unit could cause water leaks, 
condensate accumulation, leaking of the refrigerant, electric shock, 
poor operation or damage to the unit itself.
Check that the installation has been implemented by qualified 
technical personnel only and that the instructions contained in 
the present manual and the local regulations in force have been 
adhered to.
The installation of the unit in a place where even infrequent leaks 
of inflammable gas and the accumulation of this gas in the area 
surrounding the area occur could cause explosions or fires.
Carefully check the positioning of the unit.
The installation of the unit in a place unsuited to support its weight 
and/or guarantee adequate anchorage may result in consequent 
damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit.
Easy access to the unit by children, unauthorised persons or animals 
may be the source of accidents, some serious.
Install the unit in areas which are only accessible to authorised 
person and/or provide protection against intrusion into the danger 
zone.

General risks

Smell of burning, smoke or other signals of serious anomalies may 
indicate a situation which could cause damage to people, things or 
the unit itself.
Electrically isolate the unit (yellow-red isolator).
Contact the authorised service centre to identify and resolve the 
problem at the source of the anomaly.
Accidental contact with exchange batteries, compressors, air deliv-
ery tubes or other components may cause injuries and/or burns.
Always wear suitable clothing including protective gloves to work 
inside the danger zone.
Maintenance and repair operations carried out by non-qualified 
personnel may cause damage to persons, things or the unit itself.
Always contact the qualified assistance centre.
Failing to close the unit panels or failure to check the correct 
tightening of all of the panelling fixing screws may cause damage to 
persons, things or the unit itself.
Periodically check that all of the panels are correctly closed and 
fixed.
If there is a fire the temperature of the refrigerant could reach values 
that increase the pressure to beyond the safety valve with the 
consequent possible projection of the refrigerant itself or explosion 
of the circuit parts that remain isolated by the closure of the tap.
Do not remain in the vicinity of the safety valve and never leave the 
refrigerating system taps closed.

Electric parts

An incomplete attachment line to the electric network or with incor-
rectly sized cables and/or unsuitable protective devices can cause 
electric shocks, intoxication, damage to the unit or fires.
Carry out all of the work on the electric system referring to the 
electric layout and the present manual ensuring the use of a system 
thereto dedicated.
An incorrect fixing of the electric components cover may lead to 
the entry of dust, water etc inside and may consequently electric 
shocks, damage to the unit or fires.
Always fix the unit cover properly.
When the metallic mass of the unit is under voltage and is not 
correctly connected to the earthing system it may be as source of 
electric shock and electrocution.
Always pay particular attention to the implementation of the earth-
ing system connections.
Contact with parts under voltage accessible inside the unit after 
the removal of the guards can cause electric shocks, burns and 
electrocution.
Open and padlock the general isolator prior to removing the guards 
and signal work in progress with the appropriate sign.
Contact with parts that could be under voltage due to the start up 
of the unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the 
attachment line of the unit itself, padlock it and display the appro-
priate warning sign.

Moving parts

Contact with the transmissions or with the fan aspiration can cause 
injuries.
Prior to entering the inside of the unit open the isolater situated 
on the connection line of the unit itself, padlock and display the 
appropriate warning sign.
Contact with the fans can cause injury.
Prior to removing the protective grill or the fans, open the isolator 
on the attachment line of the unit itself, padlock it and display the 
appropriate warning sign.

Hydraulic parts

Defects in tubing, the attachments or the removal parts may cause 
a leak or water projection with the consequent damages to people, 
things or shortcircuit the unit.

Содержание ELFODuct MP 15

Страница 1: ...ELFODuct MP Installation use and maintenance manual FX HFOFSBUJPO IPSJ POUBM BOE WFSUJDBM CVJMU JO XBUFS TPVSDF EVDUBCMF UFSNJOBM GPS NFEJVN BOE MBSHF TZTUFN ELFODuct MP 15 71...

Страница 2: ...5IF EBUB DPOUBJOFE JO UIJT NBOVBM JT OPU CJOEJOH BOE NBZ CF DIBOHFE CZ UIF NBOVGBDUVSFS XJUIPVU QSJPS OPUJDF 3FQSPEVDUJPO FWFO JT QBSU JT 03 PQZSJHIU 7 5 4 Q FMUSF UBMJB...

Страница 3: ...3FDFQUJPO 1PTJUJPOJOH 8BUFS DPOOFDUJPOT FSBVMJD DPOOFDUJPOT MFDUSJDBM DPOOFDUJPOT 4UBSU VQ BJOUFOBODF FDPNNJTTJPOJOH 3FTJEVBM SJTLT JNFOTJPOBM ESBXJOHT 5FDIOJDBM JOGPSNBUJPO DDFTTPSJFT DDFTTPSJFT MFD...

Страница 4: ...JOFYQFSJFODFE QFSTPOOFM UIFZ NBZ DBVTF EBNBHFT UP UIJOHT BOE JOKVSJFT QFPQMF 1 4 Intended use 6TF UIF VOJU POMZ t DJWJM BJS DPOEJUJPOJOH t FFQ UP UIF MJNJUT GPSFTFFO JO UIF UFDIOJDBM TDIFEVMF BOE JO...

Страница 5: ...EPXO PS NBMGVODUJPO t NNFEJBUFMZ EFBDUJWBUF UIF VOJU t POUBDU B TFSWJDF DFOUSF BVUIPSJ FE CZ UIF NBOVGBDUVSFS 5IF JOTUBMMFS NVTU USBJO UIF VTFS QBSUJDVMBSMZ PO t 4UBSU VQ TIVUEPXO t 4FU QPJOUT DIBOHF...

Страница 6: ...loor air inlet 3 Built in vertical Floor air inlet Standard 4 Built in vertical Front air inlet DX Water fittings to the right SX Water fittings to the left MS Standard supply References for position...

Страница 7: ...EJTDPOOFDUFE SPVUFT GMJH UT TUFQT EPPST 4VJUBCMZ QSPUFDU UIF VOJU UP QSFWFOU EBNBHF P OPU MFBWF UIF QBDLBHFT MPPTF P OPU NPWF UIF VOJUT BMPOF PS TFWFSBM VOJUT VTF B TVJUBCMF DPOUBJOFS 3 3 Packaging re...

Страница 8: ...UIF VOJU BOE PG UIF GVODUJPOBM DMFBSBODFT UP BMMPX UIF BDDFTT XJUI MBEEFST PS PUIFS NFBOT 4 2 Positioning 6OJUT BSF EFTJHOFE UP CF JOTUBMMFE t 5 3 t JO GJ FE QPTJUJPOT 5IF VOJU DBO OPU CF JOTUBMMFE PV...

Страница 9: ...PS DPNGPSU BOE FOFSHZ DPOTVNQUJPO 5IF UIFSNPTUBU TIPVME CF QMBDFE t JO B SPPN XJUI NFEJVN UFNQFSBUVSF BOE IVNJEJUZ DPOEJUJPOT SFQSFTFOUBUJWF PG UIF PUIFS SPPNT t BU B IFJHIU PG DN t QSFGFSBCMZ PO BO J...

Страница 10: ...GVMMZ XBTI UIF TZTUFN CZ GJMMJOH JU BOE FNQ ZJOH JU TFWFSBM UJNFT XJUI DMFBO XBUFS YFDVUF MFBLBHF UFTU CFGPSF JTPMBUF UIF QJQFT TPMBUF UIF QJQFT UP BWPJE IFBU EJTQFSTJPOT BOE GPSNBUJPO PG DPOEFOTBUF F...

Страница 11: ...1SFWFOU UIF SJTL PG GSFF F JG UIF VOJU ESBJO PS QMVNCJOH DPOOFDUJPOT DBO CF TVCKFDU UP UFNQFSBUVSFT DMPTF UP PS FYBNQMF t TBGFHVBSE UIF QJQFT XJUI IFBUJOH DBCMFT QMBDFE VOEFS UIF JOTVMBUJPO PS t JOTVM...

Страница 12: ...UFE UPXBSET VOJU UP BWPJE UIF DPOEFOTBUF BOE XBUFS SFUVSO t MJNJU UIF MPBE MPTTFT CZ PQUJNJTJOH UIF QBUI UIF UZQF BOE OVNCFS PG CFOET BOE KVODUJPOT t VTF XJEF CFOET FWBMVBUJOH UIF PQQPSUVOJUZ PG FRVJQ...

Страница 13: ...XFS TVQQMZ MJOF EJNFOTJPOJOP 7 2 Connections 3FGFS UP UIF VOJU FMFDUSJDBM EJBHSBN UIF OVNCFS PG UIF EJBHSBN JT TIPXO PO UIF TFSJBM OVNCFS MBCFM 7FSJGZ UIBU UIF FMFDUSJDBM TVQQMZ IBT DIBSBDUFSJTUJDT DP...

Страница 14: ...OFDUJPO QPXFS TVQQMZ GFBUVSFT FMFDUSJDBM DPOOFDUJPOT QSPWJEFE CZ UIF DVTUPNFS 8 3 Start up sequence PS EFUBJMT SFGFS Uo the diffFSFOU NBOVBM TFDUJPOT Unit ON power supply PGG MPBE PMUBHF NFBTVSF VOJU...

Страница 15: ...QFDUJWF QBSBNFUFST iFMFDUSJDBM DPOOFDUJPOTw TFDUJPO BOE GPMMPXJOH QBHFT 8 8 Start up report EFOUJGZJOH UIF PQFSBUJOH PCKFDUJWF DPOEJUJPOT JT VTFGVM UP DPOUSPM UIF VOJU PWFS UJNF 8JUI VOJU BU TUFBEZ TU...

Страница 16: ...JOVPVT PS WFSZ JOUFSNJUUFOU VTF OFBS UIF PQFSBUJOH MJNJUT FUD t DSJUJDBM VTF TFSWJDF OFDFTTBSZ 9 3 Unit booklet U T BEWJTBCMF UP DSFBUF B VOJU CPPLMFU UP UBLF OPUFT PG UIF VOJU JOUFSWFOUJPOT O UIJT XB...

Страница 17: ...POUBDU XJUI UIF FYDIBOHFS GJOT DBO DBVTF DVUT FBS QSPUFDUJWF HMPWFT UP QFSGPSN UIF BCPWF EFTDSJCFE PQFSBUJPOT U JT FYUSFNFMZ JNQPSUBOU UIBU UIF CBUUFSZ HJWFT UIF NBYJNVN UIFSNBM FYDIBOHF UIFSFGPSF JUT...

Страница 18: ...VOJU 5IF GSFRVFODZ XJUI XIJDI UIF GJM FST NVTU CF DIFDLFE EFQFOET PO UIF RVBMJUZ PG UIF BJS UIF VOJU PQFSBUJPO IPVST UIF EVTUJOFTT BOE DSPXEJOH PG SPPNT SFRVFODZ DBO JOEJDBUJWFMZ WBSZ GSPN 8 UP 0 5 U...

Страница 19: ...t the fan rotation The unit does not heat up as before Hot water supply lack Wrong setting on control panel Make sure that Make sure that Make sure that Control the boiler and the hot water pump See c...

Страница 20: ...SFE CZ UIF MFHJTMBUJPO JO RVFTUJPO BSF NBSLFE XJUI UIF TZNCPM PO UIF TJEF 8JUI UIF BJN PG QSPUFDUJOH UIF FOWJSPONFOU BMM PG PVS VOJUT BSF QSPEVDFE JO DPNQMJBODF XJUI JSFDUJWF PO XBTUF FMFDUSJDBM BOE F...

Страница 21: ...tions carried out by non qualified personnel may cause damage to persons things or the unit itself Always contact the qualified assistance centre Failing to close the unit panels or failure to check t...

Страница 22: ...JOUBLF 31 MPPS BJS JOMFU 3 4UBOEBSE TVQQMZ CC2 INH Size 15 21 25 31 41 51 61 71 A Length mm 800 800 800 1200 1200 1200 1600 1600 B Width mm 555 555 555 555 555 555 555 555 C Height mm 250 250 250 250...

Страница 23: ...PS BJS JOMFU 3 4UBOEBSE TVQQMZ CC2 INV Size 15 21 25 31 41 51 61 71 A Length mm 800 800 800 1200 1200 1200 1600 1600 B Width mm 250 250 250 250 250 250 250 250 C Height mm 580 580 580 580 580 580 580...

Страница 24: ...VUMFU QJQF TZTUFN w POEFOTBUJPO ESBJOBHF NN 4UBOEBSE BJS JOUBLF 31 MPPS BJS JOMFU 3 4UBOEBSE TVQQMZ CC4 INH Size 15 21 31 41 51 61 A Length mm 800 800 1200 1200 1600 1600 B Width mm 555 555 555 555 55...

Страница 25: ...UMFU QJQF TZTUFN w POEFOTBUJPO ESBJOBHF NN 4UBOEBSE BJS JOUBLF 31 MPPS BJS JOMFU 3 4UBOEBSE TVQQMZ CC4 INV Size 15 21 31 41 51 61 A Length mm 800 800 1200 1200 1600 1600 B Width mm 250 250 250 250 250...

Страница 26: ...20 20 20 20 20 Power supply Standard power supply V 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Noise Levels Sound pressure level 1 m 6 dB A 53 54 54 60 61 61 59 59 Sound...

Страница 27: ...63 66 61 60 58 52 49 65 54 31 63 67 71 67 65 63 58 56 71 60 41 64 68 72 68 66 63 58 57 72 61 51 64 68 72 68 66 63 58 57 72 61 61 66 68 70 67 65 62 57 53 70 59 71 66 68 70 67 65 62 57 53 70 59 Max spee...

Страница 28: ...ain 5 20 20 20 20 20 20 Power supply Standard power supply V 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Noise Levels Sound pressure level 1 m 6 dB A 53 54 60 61 58 59 Sound power in the duc...

Страница 29: ...63 66 61 60 58 52 49 65 54 31 63 67 71 67 65 63 58 56 71 60 41 64 68 72 68 66 63 58 57 72 61 51 64 68 72 68 66 63 58 57 72 61 61 66 68 70 67 65 62 57 53 70 59 71 66 68 70 67 65 62 57 53 70 59 Max spee...

Страница 30: ...system 2V2 ON OFF 2 way valve kit for 2 pipe system 2V4 ON OFF 2 way valve kit for 4 pipe system BRV Auxiliary condensate collection pan vertical installation BRO Auxiliary drain pan in galvanized ste...

Страница 31: ...5IF UFNQFSBUVSF DBO CF DIBOHFE CZ JO SFMBUJPO UP UIF DPNGPSU DPOEJUJPO CZ UVSOJOH UIF LOPC t BVUPNBUJD TFMFDUJPO PG UIF 4VNNFS 8JOUFS TFBTPO UIF IFBUJOH PS DPPMJOH NPEF JT TFMFDUFE BVUPNBUJDBMMZ CZ EF...

Страница 32: ...E QBJS DBCMF BU B NBYJNVN EJTUBODF PG N 15 5 HIDT3X HID T3 electronic room control 5IF 5 SPPN DMJNBUF DPOUSPM NBLFT JU QPTTJCMF UP JOUFSGBDF XJUI UIF SFHVMBUJPO NPEVMF PG VOJUT FRVJQQFE XJUI MJWFU 5BM...

Страница 33: ...PVUMFU HSJMMF t NBOBHFNFOU PG EJBHOPTUJDT XJUI TQFDJGJD PEF GPS UZQF PG FSSPS JNFOTJPOT Y Y NN 5IF UIFSNPTUBU JT DPOOFDUFE UP UIF VOJU WJB B TIJFMEFE UXJTUFE QBJS DBCMF BU B NBYJNVN EJTUBODF PG N 5IF...

Страница 34: ...FU CZ QBSBNFUFS 16 5 Operation 5IF VOJU IBT TFU QPJOUT POF GPS IFBUJOH BOE POF GPS DPPMJOH 5IF GJSTU POF JT BV PNBUJDBMMZ LFQU MPXFS UIBO UIF TFDond one with a diffFSFODF PG BU MFBTU 5IF SFHVMBUJPO NP...

Страница 35: ...F UIF DPPMJOH IFBUJOH NPEFT BSF EFGJOFE POMZ JG Q XFS JT EFNBOEFE O UIJT PQFSBUJPO UZQF 00 BOE 5 TFUT BSF BDUJWBUFE TJNVMUBOFPVTMZ XIFO POF PG UIF TFU JT CZQBTTFE XBUFS UFNQFSBUVSF JT EFUFDUFE BOE UIF...

Страница 36: ...MOTE starts flashing Switch the unit to ECO mode Press the ECO key Repeat the operation to restore the standard operation The ECO summer set point is higher than the SUMMER set point the ECO winter se...

Страница 37: ...sor alarm CO mode change in progress for the automatic mode is not an alarm EHH lack of communication wrong thermostat connection SYS fault internal to the control module ERR configuration error 16 13...

Страница 38: ...status at cooling thermoregulator satisfied 0 stop 1 continuous 2 periodical 0 2 num 2 P22 FanOffHeat Fan status at heating thermoregulator satisfied 0 stop 1 continuous 2 periodical 0 2 num 0 P31 Mo...

Страница 39: ...JSFE IVNJEJUZ UFNQFSBUVSF t UIF EFTJSFE UZQF PG WFOUJMBUJPO t B TFSJFT PG BEWBODFE GVODUJPOT GPS UIF VOJU UP XIJDI JU JT DPOOFDUFE t EJTQMBZ BOZ FSSPS DPEFT UIBU DPSSFTQPOE UP BMBSNT TFOU CZ UIF BEKVT...

Страница 40: ...V QSFTT UIF LFZ ZPV DBO TFMFDU UIF EFTJSFE PQFSBUJOH NPEF JO UIF GPMMPXJOH DZDMJDBM TFRVFODF Heating Heating Economic Cooling Cooling Economic Ventilation 8IFO ZPV QSFTT UIF LFZ ZPV DPOGJ N UIF EJTQMB...

Страница 41: ...UJWBUF EFBDUJWBUF UIF 4XJOH GVODUJPO CZ TJNVMUBOFPVTMZ QSFTTJOH UIF LFZT BOE 5IFSF JT OP JOEJDBUJPO PO UIF EJTQMBZ GPS UIF BDUJWBUJPO EFBDUJWBUJPO PG UIJT GVODUJPO 16 32 Battery check BDI UJNF JU JT Q...

Страница 42: ...I B UPPM 16 35 Cooling 5IF WFOUJMBUJPO JT BDUJWBUFE JG t 5 0 1 BYI P PPM t 5 0 5 BNCJFOUF JG UIF UFNQFSBUVSF JT PVU PG UIFTF MJNJUT XIFO UIF EFMBZ UJNF JT GJOJTIF UIF 0 BMBSN JT BDUJWBUFE 16 36 Heatin...

Страница 43: ...0 volt OUFHSBUJPO BJO FMFNFOU 4JOHMF QIBTF 5XP QIBTF 5IF XBUFS WBMWF JT PQFOFE XIFO UIFSNP SFHVMBUJPO JT EFNBOEFE JG UIF QSPCF EFUFDUT IPU XBUFS UIF SFTJTUPST BVUPNBUJDBMMZ CFDPNF BO JOUFHSBUJPO CPEZ...

Страница 44: ...UIF PX JNJU WBMVF UIFSFGPSF UIF QSPDFTT DBO TUBSU BHBJO POMZ JG BNCJFOU UFNQFSBUVSF TFU QPJOU 5FNQ BOE JG UIFSF JT TUJMM B EFNBOE 5IF EFIVNJEJGJD UJPO QSPDFTT DBO OPU TUBSU JG t UIF PQFSBUJPO NPEF JT...

Страница 45: ...485 SERIAL LINE General indications CLIVET SPA is not responsible for any malfunctioning due to the inobservance of the recommendations of this chapter moreover it will not perform any set ups of the...

Страница 46: ...single serial line 1000 m Difference in potential between the earth of the two RS485 devices lower than 7 v Provide guards to protect against electrostatic discharges of atmospheric origin Complete l...

Страница 47: ...previous mode particularly in the two following cases master unit with under process change over master unit in water alarm Alarms The alarm displayed on the thermostat is relevant only to the master...

Страница 48: ...romagnetica Elektromagnetische Vertr glichkeit compatibilit lectromagn tique compatibilidad electromagn tica 2014 68 UE see Art 4 3 or Art 1 2 f i come da Art 4 3 o Art 1 2 f i gem Art 4 3 oder Art 1...

Страница 49: ...opposite shoulder and corresponding to the coil hydraulic connections I Open the pre punched hole arranged on the opposite shoulder and corresponding to the drain pipe L 5 Reverse the direction of th...

Страница 50: ...created in the point no 4 Tighten the 4 3 9x9 5 screws C in the aligned shoulder coil bracket holes 2 left side 2 right side Note opposite operation of point no 2 re use the same screws 9 Put back the...

Страница 51: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL...

Страница 52: ...BSDFMPOB TQB B 5FM BY JOGP DMJWFUDPNFSDJBM DPN CLIVET ESPA A S A U Service and Maintenance Division BMMF 3FBM EF VSHPT 1BSBDVFMMPT EFM BSBNB BESJE TQB B 5FM BY JOGP DMJWFU FT CLIVET GmbH VNNFMTC UUFMF...

Отзывы: