U I A
6
AWR MTD - AWR MTD/B
GB 01/2009
DIMENSIONAL DRAWINGS
I
600
W1
W2
W4
W3
900
D
B
C
=
E
A
=
400
Dimensions
0011
0025
0031
0041
0051
0061
A mm
900
900
900
900
900
900
B
mm
940
1240
1240
1240
1400
1400
C
mm
370
420
420
420
420
420
D mm
320
370
370
370
370
370
E
mm
580
580
580
580
580
580
Weight distribution AWR
0011
0025
0031
0041
0051
0061
W1 lato rear dx
kg
47
62
64
65
68
71
W2 lato rear sx
kg
23
18
20
22
24
24
W3 front sx
kg
13
18
18
21
22
22
W4 front dx
kg
42
52
53
57
61
63
tot
kg
125
150
155
165
175
180
1 - Water connections IN 0011÷0025 Ø1” - 0031÷0061 Ø1”1/4
1 - Water connections OUT 0011 Ø3/4” - 0025÷0061 Ø1”1/4
INSTALLATION
I
CHOICE OF INSTALLATION SITE
Before installing the unit, agree with the customer the site
where it will be installed, taking the following points into con-
sideration:
- Check that the fixing points are adequate to support the
weight of the unit;
- Pay scrupulous respect to safety distances between the
unit and other equipment or structures to ensure that air
entering the unit and discharged by the fans is free to cir-
culate.
- Follow the instructions shown in the chapter on DIMEN-
SIONAL DRAWINGS to allow room for maintenance oper-
ations. If installing multiple units the clearances must be
doubled.
POSITIONING
Before handling the unit, check the capacity of the lift equip-
ment used, respecting the instructions on the packaging.
To move the unit horizontally, make appropriate use of a lift
truck or similar, bearing in mind the weight distribution of the
unit.
To lift the unit, insert tubes long enough to allow positioning
of the lifting slings and safety pins in the special holes in the
base of the unit.
To avoid the slings damaging the unit, place protection
between the slings and the unit.
The unit should be installed on special vibration dampers.
See the chapter on DIMENSIONAL DRAWINGS for the sup-
port positions identified by W1, W2 etc. and the correspond-
ing weights for the correct sizing of the vibration dampers.
Fix the unit, making sure it is level and that there is easy
access to water and electrical components.
If the site is exposed to strong winds, fix the unit adequately
using tie rods if necessary.
In heating mode the unit produces a significant quantity of
condensate, which must be suitably drained.
Condensate drainage must not cause problems to objects or
people.
If the outside air temperature is less than 0°C, the conden-
sate may freeze; in these case fit a frost protection heater
on the drain line.
For correct operation of the unit, avoid the following: obsta-
cles to air flow, leaves that may block the heat exchange
coil, strong winds that stop or reinforce air flow, sources of
heat too close to the unit, recirculation or stratification of air.