ACCURATE AX - AW - AD - AT - AF
11
*WARNING, THE DIAMETERS OF THE CONNECTION LINES BETWEEN THE INDOOR UNIT AND DRY COOLER MUST BE SIZED
BY THE INSTALLER BASED ON THE INSTRUCTIONS SHOWN IN THE PARAGRAPH ON WATER CONNECTIONS
1 - air 24°C-50%, water 30-35°C - ESP 20 Pa
2 - inlet water 10°C and same flow-rate as calculated for DX operation - ESP 20 Pa
5 - Average sound pressure level, at a distance of 2 m, for units in a free field on a reflecting surface.
The average sound pressure level is calculated based on the sound power level measured in accordance with ISO 3744.
1 - air 24°C-50%, water 30-35°C - ESP 20 Pa
5 - measured at a height of 1.5 m and 2 m from the front of the unit in free field
ACCURATE - AF Water-cooled direct expansion unit with indirect free cooling
Model
20
26
29
39
30
40
50
60
70
80
90
Frame
F3
F4
F5
F6
No. of circuits / no. of compressors
1/1
1/1
1/1
1/1
2/2
2/2
2/2
2/2
2/2
2/2
2/2
Refrigerant
R410A
Rated air flow-rate
mc/h
6000
7500
8000
13000
10000
13000
13500
18000
19000
24000
24000
Power supply
V/Ph/Hz
400/3N/50
CAPACITY DELIVERED (DX)
Gross total capacity (1)
kW
24,9
30,6
32,3
47,3
38,1
50,0
54,5
70,3
76,6
91,8
101,9
Gross sensible capacity (1)
kW
22,8
28,3
30,0
46,9
36,7
47,9
50,7
66,8
71,1
88,2
92,2
SHR
0,92
0,92
0,93
0,99
0,96
0,96
0,93
0,95
0,93
0,96
0,90
Compressor power consumption
kW
4,40
5,40
6,11
8,00
6,44
8,61
10,55
12,28
13,30
16,03
19,33
Power cons. with std. EC radial fans
kW
1,35
1,80
1,80
3,20
1,30
3,20
3,20
4,50
4,50
6,10
6,10
Power cons. with HP EC radial fans
kW
0,89
1,69
1,69
3,51
2,09
3,51
3,51
5,11
5,11
6,72
6,72
Water flow-rate (1)
l/h
5080
6240
6650
9580
3865x2
5075x2
5625x2
7155x2
7795x2
18640
21000
Pessure drop Dp (1)
kPa
50
71
45
66
50
61
52
63
68
54
69
Power supply
V/Ph/Hz
460/3/60
CAPACITY DELIVERED (DX)
Gross total capacity (1)
kW
25,6
29,4
32,3
48,9
39,8
51,4
52,5
70,5
79,8
95,9
103,4
Gross sensible capacity (1)
kW
23,1
27,7
30,0
48,1
37,6
48,7
49,9
66,9
72,5
88,0
90,6
SHR
0,90
0,95
0,93
0,98
0,94
0,95
0,95
0,95
0,91
0,92
0,88
Compressor power consumption
kW
4,66
5,29
6,39
8,49
8,14
9,09
10,17
12,89
14,15
16,67
18,85
Power cons. with std. EC radial fans
kW
1,35
1,80
1,80
3,20
1,30
3,20
3,20
4,50
4,50
6,10
6,10
Power cons. with HP EC radial fans
kW
0,89
1,69
1,69
3,51
2,09
3,51
3,51
5,11
5,11
6,72
6,72
Power supply
V/Ph/Hz
380/3/60
CAPACITY DELIVERED (DX)
Gross total capacity (1)
kW
25,8
29,5
32,4
49,0
39,8
51,7
52,7
70,7
80,1
95,3
103,0
Gross sensible capacity (1)
kW
23,2
27,8
30,1
48,1
37,6
48,8
50,0
67,0
72,5
87,7
90,4
SHR
0,90
0,94
0,93
0,98
0,94
0,95
0,95
0,95
0,91
0,92
0,88
Compressor power consumption
kW
4,77
5,37
6,53
8,76
7,12
9,30
10,35
13,12
14,65
17,72
19,81
Power cons. with std. EC radial fans
kW
1,35
1,80
1,80
3,20
1,30
3,20
3,20
4,50
4,50
6,10
6,10
Power cons. with HP EC radial fans
kW
0,89
1,69
1,69
3,51
2,09
3,51
3,51
5,11
5,11
6,72
6,72
Power supply
V/Ph/Hz
230/3/60
CAPACITY DELIVERED (DX)
Gross total capacity (1)
kW
25,9
29,4
32,5
49,0
40,4
51,9
52,8
71,0
80,1
95,9
103,0
Gross sensible capacity (1)
kW
23,3
27,8
30,1
48,1
37,9
49,0
50,0
67,1
72,5
88,0
90,4
SHR
0,90
0,94
0,93
0,98
0,94
0,94
0,95
0,95
0,91
0,92
0,88
Compressor power consumption
kW
4,76
5,43
6,54
8,76
7,06
9,30
10,47
13,14
14,65
16,67
19,81
Power cons. with std. EC radial fans
kW
1,20
1,97
1,97
3,50
2,10
3,50
3,50
4,90
4,90
7,60
7,60
Power cons. with HP EC radial fans
kW
0,99
1,76
2,01
3,66
2,14
3,66
3,95
4,86
5,63
7,10
7,10
CAPACITY DELIVERED IN FREE COOLING MODE
Gross total capacity (2)
kW
19,95
24,04
25,10
40,79
33,62
41,47
43,80
56,62
58,10
76,67
78,26
Gross sensible capacity (2)
kW
19,95
24,04
25,10
40,79
33,62
41,47
43,80
56,62
58,10
76,67
78,26
SHR
1
1
1
1
1
1
1
1
1
1
1
Pressure drop in FC operation
kPa
65
90
86
85
64
84
100
90
103
66
83
Total water content
l
10
10
10
18
18
17
17
22
23
28
29
FANS
No. of std. EC radial fans
1
1
1
2
2
2
2
3
3
3
3
No. of HP EC radial fans
1
1
1
2
2
2
2
3
3
4
4
Sound pressure level (5)
dB(A)
56
60
60
64
59
64
64
67
67
67
67
PLATE CONDENSER
Type
AISI316 plate heat exchanger
Number
1
1
1
1
1
1
1
1
1
2
2
Water content
l
0,8
0,8
0,8
3,9
3,9
2,5
2,5
3
3,8
2x1,6
2x2,5
CONNECTIONS
Water connections *
IN
1"1/2 F
1"1/2 F
1"1/2 F
1"1/2 F
1"1/2 F
1"1/2 F
1"1/2 F
2" F
2" F
2" F
2" F
OUT
1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M
2" M
2" M
HUMIDIFIER
Capacity
kg/h
5
5
5
5
5
5
5
8
8
8
8
ELECTRIC HEATERS
Steps
3
3
3
3
3
3
3
3
3
3
3
Heating capacity
kW
9
9
9
15
15
15
15
18
18
18
18
DIMENSIONS
Length
mm
1000
1550
2100
2650
Depth
mm
790
790
790
790
Height
mm
1980
1980
1980
1980
OUTDOOR UNIT COMBINATIONS
BDC Dry Cooler
030m
039m
039m
052m
039m
052m
062m
078m
092m
103m
123m