ATW wall-mounted control
The ATW control is used to regulate the air (3 auto), the temperature through electronic thermostat, to select the sum-
mer/winter/auto mode of operation and to switch the fan coil on/off.
Temperature selector
Adjust the temperature as
required by turning the
temperature selector from +14°C
to 30°C.
Function selector
Select the mode of operation
pushing the
buttom.
Cooling
Heating
Off
Automatic setting
Speed selector
Select the fan speed pushing the
buttom.
The repeated pressure of fan button
determines speed required.
Maximum fan speed
Medium fan speed
Minimum fan speed
Automatic fan speed
Led
Blue LED: Heating / Cooling
plus regulator call
Blue LED blinking: Hot start / Too Cool
function active
Blue LED:
operation in Cooling mode
Blue LED:
operation in Heating mode
Blue LED:
automatic cooling / heating
mode selection
Technical data
Supply voltage
230 V ~ ±10%
Supply frequency
50/60 Hz
Contact rating
1A (cosØ ≥0.85; 230V)
Remote air sensor
10 kOhm @ T = 25 °C
Remote water sensor
10 kOhm @ T = 25 °C
Regulation range
+14°C a 30°C
Storage temperature
-20 °C / +85 °C
Max. storage humidity
90% (not condensing)
Working temperature
0 °C / +55 °C
Max. working humidity
90% (not condensing)
Protection rating
IP 30
Case material
PC+ABS (flame retardant V0)
Color
RAL 9003 (white)
Dimensions
120 x 75 x 25 mm
Weight
0,265 kg