C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
48
Blower Performance Data – TSL12
Table 5i
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1" filter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%
RPM/Watt Tolerance 10%
External Static Pressure (in. wg)
PSC - High Static
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low
RPM
980
1090
1190
Operation not recommended
Power (W)
145
139
132
CFM
350
340
320
Medium
RPM
1290
1360
1440
1470
1540
1590
Power (W)
197
185
174
162
151
139
CFM
500
480
460
430
390
340
High
RPM
Operation not recommended
1590
1630
1680
Power (W)
151
151
151
CFM
520
470
390
ECM - Constant T
orque
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
RPM
1070
1140
1230
1320
1400
Operation not recommended
Power (W)
66
70
74
78
82
CFM
410
380
360
330
310
2
RPM
1140
1190
1280
1370
1430
1510
1580
Power (W)
54
58
61
65
69
73
77
CFM
450
420
400
380
360
330
310
3
RPM
1190
1240
1320
1400
1450
1530
1590
1660
Power (W)
79
83
87
91
96
100
104
108
CFM
480
460
440
420
400
370
350
330
4
RPM
Operation not recommended
1580
1630
1690
Power (W)
137
141
145
CFM
480
460
440
ECM - Constant V
olume
CFM
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
300
RPM
890
1040
1170
1300
1400
1500
1570
1660
Power (W)
38
48
58
69
81
93
105
118
350
RPM
980
1100
1220
1340
1430
1520
1590
1670
Power (W)
50
62
73
85
98
110
124
137
400
RPM
1060
1170
1280
1380
1450
1540
Power (W)
65
79
92
105
119
132
450
RPM
1140
1230
1330
1430
Power (W)
87
101
115
128
Operation not recommended
500
RPM
1220
Power (W)
111