46
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
2 0 ( T S ) S e r i e s
R e v. : 0 6 / 1 7 / 1 5
Table 6: Humidistat/Dehumidistat Logic & DXM (2.1, 2.2., 2.3) DIP Settings
Sensor
2.1
2.2
2.3
Logic
Reheat (ON) - H
Reheat (OFF) - H
Humidistat
OFF
OFF
OFF
Reverse
0 VAC
24 VAC
Dehumidistat
OFF
ON
OFF
Standard
24 VAC
0 VAC
1
Cooling input takes priority over dehumidify input.
2
DXM is programmed to ignore the H demand when the unit is in heating mode.
3
N/A for single stage units; Full load operation for dual capacity units.
4
ON/OFF = Either ON or OFF.
Mode
Input
Output
O
G
Y1
Y2
3
H
O
G
Y1
Y2
3
Reheat
No Demand
ON/OFF
OFF
OFF
OFF
OFF
ON/OFF
OFF
OFF
OFF
OFF
Fan Only
ON/OFF
ON
OFF
OFF
OFF
ON/OFF
ON
OFF
OFF
OFF
Cooling 1st Stage
ON
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Cooling 2nd Stage
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
Cooling & Dehumidistat
1
ON
ON
ON
ON/OFF
ON
ON
ON
ON
ON/OFF
OFF
Dehumidistat Only
ON/OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
Heating 1st Stage
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
Heating 2nd Stage
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
OFF
Heating & Dehumidistat
2
OFF
ON
ON
ON/OFF
ON
OFF
ON
ON
ON/OFF
OFF
Table 7: ClimaDry
®
Operating Modes
ClimaDry
®
Modulating Reheat Option
UNIT STARTING AND OPERATING CONDITIONS
Operating Limits
Environment – Units are designed for indoor
installation only. Never install units in areas subject to
freezing or where humidity levels could cause cabinet
condensation (such as unconditioned spaces subject to
100% outside air).
Power Supply – A voltage variation of +/– 10% of
nameplate utilization voltage is acceptable.
Determination of operating limits is dependent
primarily upon three factors: 1) return air temperature. 2)
water temperature, and 3) ambient temperature. When
any one of these factors is at minimum or maximum
levels, the other two factors should be at normal levels
to ensure proper unit operation. Extreme variations in
temperature and humidity and/or corrosive water or air
will adversely affect unit performance, reliability, and
service life. Consult Table 8a for operating limits.
Air Limits
Min. ambient air, DB
Rated ambient air, DB
Max. ambient air, DB
Min. entering air, DB/WB
Rated entering air, DB/WB
Max. entering air, DB/WB
Water Limits
Min. entering water
Normal entering water
Max. entering water
Operating Limits
Normal Water Flow
Cooling
Heating
45ºF [7ºC]
39ºF [4ºC]
80.6ºF [27ºC]
68ºF [20ºC]
130ºF [54.4ºC]
85ºF [29ºC]
*60/50ºF [16/10ºC]
45ºF [7ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
120ºF [49ºC]
90ºF [32ºC]
TS
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Table 8a: Operating Limits
*If with ClimaDry® 65/55ºF (18/13ºC)
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
Max. ambient air, DB
130ºF [54.4ºC]
85ºF [29ºC]
Min. entering air, DB/WB
*50/45ºF [10/7ºC]
40ºF [4.5ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
Max. entering air, DB/WB
110/83ºF [43/28ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
Commissioning Limits
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
*If with ClimaDry
®
65/55ºF (18/13ºC)
Table 8b: Building Commissioning Limits
Commissioning Conditions
Consult Table 8b for the particular model. Starting
conditions vary depending upon model and are based
upon the following notes:
Notes:
1. Conditions in Table 8b are not normal or continuous
operating conditions. Minimum/maximum limits are
start-up conditions to bring the building space up to
occupancy temperatures. Units are not designed to
operate under these conditions on a regular basis.
2. Voltage utilization range complies with AHRI
Standard 110.