background image

9

R e m o t e   H W G

R e v i s e d :   M a rc h   1 2 ,   2 0 1 9

c l i m a t e m a s t e r. c o m

Hot Water Generator Module - Domestic Water Installation

Table 2: HWG Water Piping Size and Length

Unit 

Nominal 

Tonnage

Nominal 

HWG Flow 

(gpm)

1/2" Copper 

(max length*)

3/4" Copper 

(max length*)

1.5

0.6

50

-

2.0

0.8

50

-

2.5

1.0

50

-

3.0

1.2

50

-

3.5

1.4

50

-

4.0

1.6

45

50

5.0

2.0

25

50

6.0

2.4

10

50

*Maximum length is equivalent length (in feet) one way of type L 

copper.

 

CAUTION! 

CAUTION!

 Use only copper piping for HWG piping due to 

the potential of high water temperatures for water that has 
been in the HWG heat exchanger during periods of no-

fl

 ow 

conditions (HWG pump not energized).  Piping other than 
copper may rupture due to high water temperature and 
potable water pressure.

Warning!  The HWG pump Is fully wired from the 
factory.  Use extreme caution when working around 
the microprocessor control as it contains line voltage 
connections that presents a shock hazard that can 
cause severe injury or death!

The heat pump, water piping, pump, and hot water tank 
should be located where the ambient temperature does 
not fall below 50°F [10°C]. Keep water piping lengths at a 
minimum. DO NOT use a one way length greater than 50 ft. 
(one way) [15 m]. See Table 2 for recommended piping sizes 
and maximum lengths.

All installations must be in accordance with local codes. The 
installer is responsible for knowing the local requirements, 
and for performing the installation accordingly. DO NOT 
energize the pump until “water tank re

fi

 ll” section, below is 

completed. Powering the pump before all installation steps 
are completed may damage the pump.

Water Tank Preparation

1. Turn 

o

  power or fuel supply to the hot water tank.

2.  Connect a hose to the drain valve on the water tank.
3. Shut 

o

  the cold water supply to the water tank.

4.  Open the drain valve and open the pressure relief valve 

or a hot water faucet to drain tank.

5.  When using an existing tank, it should be 

fl

 ushed with 

cold water after it is drained until the water leaving the 
drain hose is clear and free of sediment.

6.  Close all valves and remove the drain hose.
7.  Install HWG water piping.

HWG Water Piping

1.  Using at least 5/8” [16mm] O.D. copper, route and install 

the water piping and valves as shown in Figures 1 or 2. 
Install an approved anti-scald valve if the 150°F HWG 
setpoint is or will be selected. An appropriate method 
must be employed to purge air from the HWG piping. 
This may be accomplished by 

fl

 ushing water through the 

HWG (as In Figures 1 and 2) or by Installing an air vent at 
the high point of the HWG piping system.

2.  Insulate all HWG water piping with no less than 3/8” 

[10mm] wall closed cell insulation.

3.  Open both shut o

  valves and make sure the tank drain 

valve is closed.

Water Tank Refi ll 

1.  Close valve #4.  Ensure that the HWG valves (valves #2 

and #3) are open. Open the cold water supply (valve #1) 
to 

fi

 ll the tank through the HWG piping. This will purge air 

from the HWG piping.

2.  Open a hot water faucet to vent air from the system until 

water 

fl

 ows from faucet; turn o

  faucet. Open valve #4.

3.  Depress the hot water tank pressure relief valve handle to 

ensure that there is no air remaining in the tank.

4.  Inspect all work for leaks.
5.  Before restoring power or fuel supply to the water heater, 

adjust the temperature setting on the tank thermostat(s) 
to insure maximum utilization of the heat available from 

the refrigeration system and conserve the most energy. 
On tanks with both upper and lower elements and 
thermostats, the lower element should be turned down 
to 100°F [38°C] or the lowest setting; the upper element 
should be adjusted to 120-130°F [49-54°C]. Depending 
upon the speci

fi

 c needs of the customer, you may want 

to adjust the upper element di

 erently. On tanks with a 

single thermostat, a preheat tank should be used (Fig 2).

6.  Replace access cover(s) and restore power or 

fuel supply.

Initial Start-Up

1.  Make sure all valves in the HWG water circuit are fully 

open.

2. Turn the heat pump power and remote HWG power “o

 ” 

and switch dip switch DIP 3.4 on the HWG controller to 
the “o

 ” (enabled) position to activate the HWG.

3. The HWG pump should not run if the compressor is not 

running.

4. The temperature di

 erence between the water entering 

and leaving the HWG should be approximately 5-10 

°

[3-6 

°

C].

5.  Allow the unit to operate for 20 to 30 minutes insure that 

it is functioning properly.

6.  Always turn dip switch DIP 3.4 on the HWG controller to 

the “on” (disabled) position to deactivate the HWG when 
servicing the outdoor compressor section.

Содержание AHWG

Страница 1: ...Maintenance Instructions 97B0072N05 Revised March 12 2019 Table of Contents Model Nomenclature Example 3 Description and Installation Examples 4 Water Quality Requirements 5 Installation and Operatin...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...atemaster com Model Nomenclature for Remote Hot Water Generator AHWG 1 1 2 3 4 5 Accessory AHWG Accessory Remote Hot Water Generator Size B 6 Revision A 7 S 8 9 Future Voltage S 1 Standard B Current R...

Страница 4: ...om the HWG For example consider the amount of heat that can be generated by the HWG when using the 125 F set point versus the amount of heat that can be generated by the HWG when using the 150 F set p...

Страница 5: ...150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a maximum...

Страница 6: ...be located where the ambient temperature does not fall below 50 F 10 C Keep water piping lengths at a minimum DO NOT use a one way length greater than 50 ft one way 15 m See Table 2 for maximum water...

Страница 7: ...d Figure 3b Remote HWG Module Capacity Line Set Size 1 2 OD 5 8 OD 3 4 OD 2 Ton Up to 16 ft 4 9m Up to 30 ft 9 1m N A 3 Ton Up to 9 ft 2 7m Up to 25 ft 7 6m Up to 30 ft 9 1m 4 Ton Up to 5 ft 1 5m Up t...

Страница 8: ...control has detected a HWG fault the DXM2 status LED will flash a numeric fault code as follows High Water Temperature 160 F 5 flashes Hot Water Sensor Fault 6 flashes Compressor Discharge Sensor Faul...

Страница 9: ...m O D copper route and install the water piping and valves as shown in Figures 1 or 2 Install an approved anti scald valve if the 150 F HWG setpoint is or will be selected An appropriate method must b...

Страница 10: ...tors for field installed electrical wiring Unit terminals are not designed to accept other types of conductors 208 230 Volt Operation Verify transformer tap with air handler wiring diagram to insure t...

Страница 11: ...cal shock open the power supply disconnect switch and secure it in an open position during installation CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not...

Страница 12: ...Re mot e HWG R evise d March 12 2019 12 Geothermal Heat Pump Systems Outdoor Split TEP DXM2 Wiring Diagram with Internal Flow Controller 96B0005N65...

Страница 13: ...13 Remote H W G Revised Marc h 1 2 2 0 1 9 climatemaster com 115V Hot Water Generator Wiring Diagram 96BN0141N11 Figure 7 TEP...

Страница 14: ...Re mot e HWG R evise d March 12 2019 14 Geothermal Heat Pump Systems 230V Hot Water Generator Wiring Diagram 96BN0141N12 Figure 8 TEP...

Страница 15: ...0ROG IXQJXV RU EDFWHULD GDPDJHV RUURVLRQ RU DEUDVLRQ RI WKH SURGXFW 3URGXFWV VXSSOLHG E RWKHUV 3URGXFWV ZKLFK KDYH EHHQ RSHUDWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLRQV 3URGXFWV ZKLFK KDYH LQV...

Страница 16: ...mation on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely...

Отзывы: