background image

R e m o t e   H W G

R e v i s e d :   M a rc h   1 2 ,   2 0 1 9

4

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

+RW2XWOHW

WRKRPH

,QVXODWHGZDWHUOLQHV
µ2'IWPD[LPXPRQHZD\PHWHUV
>PP2'PHWHUVPD[LPXP@

3RZHUHG

:DWHU

+HDWHU

8SSHU

HOHPHQWWR

120 - 130°

[49 - 54°C

/RZHU

HOHPHQWWR

100 - 110°F

[38 - 43°C

Cold Inlet from

Domestic supply

Shut-off

Valve #4

Shut-off

Valve #3

Shut Off 
Valve #2

Shut-off

Valve #1

Insulated water lines - 5/8” OD, 50 ft maximum (one way)

[16mm OD, 15 meters maximum]

Upper element to 130°F [54°C]

(or owner preference)

Cold Inlet

Hot Outlet to

house

Powered

Water Heater

Cold Inlet from

Domestic supply

Hot Outlet

Unpowered

Water Heater

Field Supplied 3/4” brass nipple and “T”

Lower element to 120°F [49°C]

Shut-off

Valve #1

Shut-off

Valve #4

Shut-off

Valve #3

Shut Off 
Valve #2

Figure 1: Typical HWG Installation (Outdoor Compressor 
Section)

Figure 2: HWG Double Tank Installation (Outdoor Com-
pressor Section)

Hot Water Generator Module For
Outdoor Compressor Section

General Information

The HWG Module consists of an all-copper, vented double-
wall heat exchanger and a water-cooled bronze water 
circulating pump. The pump is controlled by DXM2 control. 
Power for the pump is provided from a remote 115 or 230 
vac power source.

The HWG (Hot Water Generator) or desuperheater option 
provides considerable operating cost savings by utilizing 
excess heat energy from the heat pump to help satisfy 
domestic hot water requirements. The HWG may be active 
throughout the year, providing virtually free hot water when 
the heat pump operates in the cooling mode or hot water at 
the COP of the heat pump during operation in the heating 
mode. Actual HWG water heating capacities are provided in 
the appropriate heat pump performance data.

The temperature set point of the HWG is 

fi

 eld selectable on 

the DXM2 to 125°F or 150°F .  The 150°F  set point allows 
more heat storage from the HWG.  For example, consider 
the amount of heat that can be generated by the HWG when 
using the 125°F set point, versus the amount of heat that can 
be generated by the HWG when using the 150°F set point.

In a typical 50 gallon two-element electric water heater 
the lower element should be turned down to 100°F, or the 
lowest setting, to get the most from the HWG.  The tank will 
eventually stratify so that the lower 80% of the tank, or 40 
gallons, becomes 100°F (controlled by the lower element).  
The upper 20% of the tank, or 10 gallons, will be maintained 
at 125°F (controlled by the upper element).

Using a 125°F set point, the HWG can heat the lower 40 
gallons of water from 100°F to 125°F, providing up to 8,330 
btu’s of heat.  Using the 150°F set point, the HWG can heat 
the same 40 gallons of water from 100°F to 150°F and the 
remaining 10 gallons of water from 125°F to 150°F, providing 
a total of up to 18,743 btu’s of heat, or more than twice as 
much heat as when using the 125°F set point.

This example ignored standby losses of the tank.  When 
those losses are considered the savings are even greater.

Electric water heaters are recommended. If a gas, propane, 
or oil water heater is used, a second preheat tank must be 
installed (Figure 2). If the electric water heater has only a 
single center element, the dual tank system is recommended 
to insure a usable entering water temperature for the HWG.

Typically a single tank of at least 52 gallons (235 liters) is used 
to limit installation costs and space. However, a dual tank, as 
shown in Figure 2, is the most e

  cient system, providing the 

maximum storage and temperate source water to the HWG.

It is always advisable to use water softening equipment on 
domestic water systems to reduce the scaling potential and 
lengthen equipment life. In extreme water conditions, it may 
be necessary to avoid the use of the HWG option since the 

potential cost of frequent maintenance may o

 set or exceed 

any savings. Consult water quality requirements table for 
scaling potential.

Содержание AHWG

Страница 1: ...Maintenance Instructions 97B0072N05 Revised March 12 2019 Table of Contents Model Nomenclature Example 3 Description and Installation Examples 4 Water Quality Requirements 5 Installation and Operatin...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...atemaster com Model Nomenclature for Remote Hot Water Generator AHWG 1 1 2 3 4 5 Accessory AHWG Accessory Remote Hot Water Generator Size B 6 Revision A 7 S 8 9 Future Voltage S 1 Standard B Current R...

Страница 4: ...om the HWG For example consider the amount of heat that can be generated by the HWG when using the 125 F set point versus the amount of heat that can be generated by the HWG when using the 150 F set p...

Страница 5: ...150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a maximum...

Страница 6: ...be located where the ambient temperature does not fall below 50 F 10 C Keep water piping lengths at a minimum DO NOT use a one way length greater than 50 ft one way 15 m See Table 2 for maximum water...

Страница 7: ...d Figure 3b Remote HWG Module Capacity Line Set Size 1 2 OD 5 8 OD 3 4 OD 2 Ton Up to 16 ft 4 9m Up to 30 ft 9 1m N A 3 Ton Up to 9 ft 2 7m Up to 25 ft 7 6m Up to 30 ft 9 1m 4 Ton Up to 5 ft 1 5m Up t...

Страница 8: ...control has detected a HWG fault the DXM2 status LED will flash a numeric fault code as follows High Water Temperature 160 F 5 flashes Hot Water Sensor Fault 6 flashes Compressor Discharge Sensor Faul...

Страница 9: ...m O D copper route and install the water piping and valves as shown in Figures 1 or 2 Install an approved anti scald valve if the 150 F HWG setpoint is or will be selected An appropriate method must b...

Страница 10: ...tors for field installed electrical wiring Unit terminals are not designed to accept other types of conductors 208 230 Volt Operation Verify transformer tap with air handler wiring diagram to insure t...

Страница 11: ...cal shock open the power supply disconnect switch and secure it in an open position during installation CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not...

Страница 12: ...Re mot e HWG R evise d March 12 2019 12 Geothermal Heat Pump Systems Outdoor Split TEP DXM2 Wiring Diagram with Internal Flow Controller 96B0005N65...

Страница 13: ...13 Remote H W G Revised Marc h 1 2 2 0 1 9 climatemaster com 115V Hot Water Generator Wiring Diagram 96BN0141N11 Figure 7 TEP...

Страница 14: ...Re mot e HWG R evise d March 12 2019 14 Geothermal Heat Pump Systems 230V Hot Water Generator Wiring Diagram 96BN0141N12 Figure 8 TEP...

Страница 15: ...0ROG IXQJXV RU EDFWHULD GDPDJHV RUURVLRQ RU DEUDVLRQ RI WKH SURGXFW 3URGXFWV VXSSOLHG E RWKHUV 3URGXFWV ZKLFK KDYH EHHQ RSHUDWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLRQV 3URGXFWV ZKLFK KDYH LQV...

Страница 16: ...mation on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely...

Отзывы: