Page 21
TROUBLESHOOTING
General
CXM board troubleshooting in general is best summa-
rized as simply varifying inputs and outputs. After this
process has been varified, confidence in board operation
is confirmed and the trouble must be else where. Below
are some general guidelines required for developing
training materials and procedures when applying the
CXM control.
Field Inputs
All inputs are 24VAC from the thermostat.and can be
varified using a volt meter between C and Y, G, O, W.
See the I/O Reference table below.
Sensor Inputs
All sensor inputs are 'paired wires' connecting each
component with the board. Therefore continuity on
pressure switches, and the condensate switch can be
checked at the board connector.
The thermistor resistance should be measured with the
connector removed so that only the impedance of the
thermistor is measured. If desired this reading can be
compared to the chart shown in the thermistor section of
this manual based upon the actual termperature of the
thermistor clip. An ice bath can be used to check
calibration of a thermistor if needed.
Outputs
The compressor relay is 24VAC and can be varified
using a voltmeter. The fan signal is passed through the
board to the external fan relay. The alarm relay can
either be 24VAC as shipped or dry contacts (measure
continuity during fault) for use with DDC by clipping the
J1 jumper. Electric heat outputs are 24VDC ground
sinking and require a voltmeter set for DC to varify
operation. See the I/O Reference table below.
Test Mode
Test mode can be entered for 20 minutes by shorting the
test pins.
Connection
Input or
O u t p u t
Description
R
-
24 VAC
C
-
24 VAC (grounded common)
Y
I
Connect to thermostat - Y output call for compressor
W
I
Connect to thermostat - W output call for Htg2 or Emerg Ht
O
I
Connect to thermostat - 0 output call for reversing valve with cooling
G
I
Connect to thermostat - G output call for fan
AL1
O
Connect to thermostat fault light - 24VAC or dry alarm
AL2
O
Alarm Relay 24VAC or dry
A
O
Output for water solenoid valve - paralleled with compressor contactor coil
BR
O
Connection for blower relay-direct connect from G
BRG
O
Blower relay common connection
CC
O
Connection for compressor contactor
CCG
O
Compressor contactor common connection
HP
I
High Pressure Switch input terminals
LP
I
Low Pressure Switch input terminals
FP1
I
Water Coil Freeze Protection Thermistor Input
FP2
I
Air Coil Freeze Protection Thermistor Input
RV
O
Reversing Valve Output Terminals - direct connect from "O"
CO
I
Condensate overflow input terminals
24VDC
O
24 VDC supply to electric heat module
W1
O
Output terminal for stage 1 electric heat
W2
O
Output terminal for stage 2 electric heat
Table 10. CXM Input/Output Reference Table