Climate Control CLIMATE CONTROL CC-CUBZTB Скачать руководство пользователя страница 9

9

H

oriz

on

tal D

ischar

ge 

Medium Temperature R-404A/R-507

*= T for Outdoors, N for Indoors, S for Beacon II

Consult factory on all models for applications above 110°F ambient.

Unit Model

Number

Compressor

Model   

   Suction Temp.

90°F

Amb.

95°F

 Amb.

100°F

 Amb.

110°F

 Amb.

°F

CB*0551M6

4C0969SH

40

30

25

20

15

5

89700 

75460 

68740 

62260 

56190 

45520

85620 

72064 

65580 

59360 

53510 

43270

81720 

68710 

62440 

56460 

50870 

41170

74280 

62010 

56230 

50730 

45720 

36550

CB*0751M6

4C1145SH

40

30

25

20

15

5

105280

88720

80750

72780

65640

53140

100690

84739

76660

69360

62500

50500

95530

80270

72960

65960

59380

47880

86960

72380

65640

59210

53160

42700

CB*0901M6

4C1385SH

40

30

25

20

15

5

129090

108780

99120

89850

81200

65960

124130

101623

94750

85870

77500

62760

118700

99390

90440

81860

73800

59840

107220

90050

81730

76750

66340

53950

CB*1001M6

4C1480PH

40

30

25

20

15

5

137470

115200

104860

94930

85670

69300

131010

107509

100040

90550

81560

65840

125080

105430

95260

86090

77450

62560

113750

94630

85740

77130

69510

55590

Performance Data

Unit Model

Number

Compressor

Model   

   Suction Temp.

90°F

Amb.

95°F

 Amb.

100°F

 Amb.

110°F

 Amb.

°F 

CB*0401L6

4C0969SL

0

35200

33380

31560

28020

-10

27690

26222

24690

21680

-15

24440

23040

21620

18870

-20

21520

20210

18930

16460

-30

17090

16000

14930

12820

-40

15030

14090

13200

11330

CB*0551L6

4C1145SL

0

42930

40770

38600

34290

-10

33890

32073

30230

26620

-15

29880

28200

26510

23190

-20

26310

24770

23230

20270

-30

20960

19650

18370

15830

-40

18450

17320

16240

14010

CB*0601L6

4C1385SL

0

52890

50250

47530

42230

-10

41590

39334

37070

32610

-15

36690

34580

32480

28460

-20

32320

30410

28510

24810

-30

25910

24260

22630

19540

-40

22910

21500

20090

17370

CB*0611L6

4C1480PL

0

56010

52610

49660

43790

-10

43740

41241

38770

33850

-15

38540

36230

33910

29460

-20

33870

31750

29680

25640

-30

26730

24980

23280

19980

-40

23080

21650

20230

17430

CB*0751L6

4C1761PL

0

68040

64570

61090

54180

-10

53710

50780

47800

41660

-15

47320

44580

41840

36480

-20

41590

39080

36600

31870

-30

32760

30720

28700

24750

-40

28200

26530

24910

21590

CB*1001L6

4C2067PL

0

78200

74200

70160

63210

-10

61470

58050

54740

48110

-15

54150

51030

47940

41820

-20

47560

44700

41880

36370

-30

37620

35240

32860

28310

-40

32550

30500

28620

24710

CB*1201L6

4C2397PL

0

93390

88580

83830

74420

-10

74920

69208

65150

57070

-15

64440

60680

56890

49580

-20

56560

53090

49680

43080

-30

44620

41750

38850

33170

-40

38400

36060

33630

28760

CB*1301L6

4B2707PL

0

105360

100530

95590

85790

-10

83410

79221

75110

66870

-15

73740

69890

66030

58590

-20

65040

61530

58040

51230

-30

51830

48880

45950

40350

-40

45050

42600

40250

35390

Low Temperature R-404A/R-507

Содержание CLIMATE CONTROL CC-CUBZTB

Страница 1: ...CC CUBZTB April 2009 v 001 AIR COOLED CONDENSING UNITS WITH BITZER COMPRESSORS Technical Guide www coldyoucancounton com CLIMATE CONTROL ...

Страница 2: ...3 to 50 HP Single Compressor Standard and Optional Features 12 Nomenclature 12 Performance Data Medium Temperature R 404A R 507 13 Low Temperature R 404A R 507 14 Electrical Data Medium Temperature R 404A R 507 15 Low Temperature R 404A R 507 15 Specifications and Dimensional Data Medium Temperature R 404A R 507 16 Low Temperature R 404A R 507 16 Vertical Air Discharge Condensing Units 26 to 100 H...

Страница 3: ...ubes are added to the condenser coil These tubes are expanded into the aluminum fins and condenser tube sheets These anchor tubes support the weight of the coil but are not a part of the refrigerant circuit The tubes in the refrigerant circuit are expanded into the fins but float through oversized holes in the tube sheets Tube sheet leaks are virtually eliminated since the tubes which carry refrig...

Страница 4: ...s Beacon II Smart II Software Beacon II Smart II Software makes it easy to adjust and monitor one or more refrigeration systems as well as capture minute by minute system conditions This Windows based software allows you to connect to the Beacon II Smart Controller from anywhere in the world to monitor the systems make adjustments and log minute by minute system conditions This data logging capabi...

Страница 5: ...ol of refrigerant head pressure without the use of special expansion valves Energy savings in mild ambient conditions due to reduced compressor discharge pressure and refrigerant subcooling Provides easy restart during low ambient conditions Operation As the ambient temperature falls the system condensing pressure is also reduced This pressure is maintained by a regulator ORI 6 65 225 at the conde...

Страница 6: ...gineering Built in America Bitzer Standard Execution Octagon 4C Models 4B 6B Models POE Oil Charge Protective Dry Nitrogen Charge Suction Discharge Service Valves Dual Voltage INT Protection Modules Terminal Box Enclosure Class IP65 Unloader Heads Patented Internal Mufflers Centrifugal Oil System Conventional Oil Pump Bitzer Options 4C Models 4B 6B Mounting Hardware Spring Kits Hard Mount Kits Opt...

Страница 7: ...calOilSensor SeeOLC K1photo below that mounts to the outer cover of the compressor and monitors oil level by means of an infrared light OLC K1 Operating Principle TheOLC K1sensingdeviceshinesaninfraredlightinto the oil reservoir If oil is present the light is absorbed and the compressor runs normally If no oil is present the light reflects on the sensor and the compressor shuts off Bitzer 4B 6B Mo...

Страница 8: ...rols including compressor contactor and optional defrost control are located in easily accessible control box with a hinged cover Service Mate module to assist troubleshooting Pumpdown Switch Cabinet is constructed from prepainted galvanized steel Base valve and high low pressure taps on outside of unit Vertical receivers Factory Installed Options Oversized receiver Replaceable core liquid filter ...

Страница 9: ... 21620 18870 20 21520 20210 18930 16460 30 17090 16000 14930 12820 40 15030 14090 13200 11330 CB 0551L6 4C1145SL 0 42930 40770 38600 34290 10 33890 32073 30230 26620 15 29880 28200 26510 23190 20 26310 24770 23230 20270 30 20960 19650 18370 15830 40 18450 17320 16240 14010 CB 0601L6 4C1385SL 0 52890 50250 47530 42230 10 41590 39334 37070 32610 15 36690 34580 32480 28460 20 32320 30410 28510 24810 ...

Страница 10: ...n II or Air Defrost Remote Loads 60 Hz RLA LRA Qty HP FLA MCA MOP Electric Defrost Evap Fan Amps Defrost Heater Amps System MCA System MOP CB 0401L6C 4C0969SL 208 230 3 16 7 142 0 1 1 3 2 7 23 6 40 0 CONTACT FACTORY FOR SYSTEM ELECTRICAL RATINGS CB 0401L6D 4C0969SL 460 3 9 0 58 0 1 1 3 1 9 13 2 20 0 CB 0401L6E 4C0969SL 575 3 7 0 51 5 1 1 3 1 2 10 0 15 0 CB 0551L6C 4C1145SL 208 230 3 19 4 163 0 1 1...

Страница 11: ... 10 0 7 8 1 5 8 67 87 41 3 4 75 1 8 48 3 4 1 101 CB 0401L6 4C0969SL 4 0 1 2 1 1 8 28 52 36 3 4 51 3 4 39 1 4 595 CB 0551L6 4C1145SL 5 5 1 2 1 1 8 28 52 36 3 4 51 3 4 39 1 4 645 CB 0601L6 4C1385SL 6 0 5 8 1 3 8 67 78 36 3 4 63 3 4 39 1 4 775 CB 0611L6 4C1480PL 6 5 5 8 1 3 8 67 78 36 3 4 63 3 4 39 1 4 865 CB 0751L6 4C1761PL 7 5 5 8 1 3 8 67 78 36 3 4 63 3 4 39 1 4 935 CB 1001L6 4C2067PL 10 0 5 8 1 3...

Страница 12: ...inged cover Service Mate module to assist troubleshooting Pumpdown Switch Cabinet is constructed from prepainted galvanized steel Convenient access panels for easy servicing to internal components Adjustable head pressure control valves Factory Installed Options Compressor unloading Replaceable core liquid filter drier Liquid line solenoid valve Suction filter Replaceable core suction filter Sucti...

Страница 13: ...980 133380 243980 204400 185400 167350 150090 119580 CDV 300BM6 4B3604PH 40 30 25 20 15 5 339410 284940 259200 235080 211960 171290 324930 273150 248290 225050 202640 163320 311370 261580 237590 214940 193290 155450 285650 238360 215910 194800 174680 139050 CDV 330BM6 6B4060PH 40 30 25 20 15 5 385050 321570 292920 263780 237640 190700 368290 308190 279790 252590 227190 181990 352830 296110 267620 ...

Страница 14: ... 40 55050 51170 47240 39070 CDV 220BL6 6B4060PL 0 156330 148990 141590 127330 10 120650 114230 107830 96230 15 104810 98870 92970 81890 20 90770 85340 79790 69200 30 69550 64720 59860 49790 40 59470 55420 51350 43220 CDV 250BL6 6B4709PL 0 184510 175840 166300 148750 10 142790 135120 127430 113350 15 124340 117270 110260 96980 20 107930 101510 94950 82350 30 83040 77430 71770 59880 40 71140 66410 6...

Страница 15: ...294 2 9 6 64 1 100 CDV 150BL6 4B3139PL 46 2 294 2 9 6 67 4 110 CDV 200BL6 4B3604PL 57 7 352 2 9 6 81 7 125 CDV 220BL6 6B4060PL 65 4 436 2 14 0 95 8 150 CDV 250BL6 6B4709PL 69 2 436 2 14 0 100 5 150 CDV 300BL6 6B5406PL 84 6 490 2 14 0 119 8 200 CDV 400BL6 6B6462PL 97 4 700 3 21 0 142 8 225 460 Volts CDV 150BM6 4C2067PH 24 4 147 2 4 8 35 3 60 CONTACT FACTORY FOR SYSTEM ELECTRICAL RATINGS CDV 200BM6 ...

Страница 16: ... 8 2 1 8 123 56 171 1 690 CDV 250BM6 4B3139PH 25 1 1 8 2 1 8 123 56 171 1 935 CDV 300BM6 4B3604PH 30 1 1 8 2 1 8 188 85 226 1 615 CDV 330BM6 6B4060PH 33 1 1 8 2 1 8 188 85 226 1 785 CDV 350BM6 6B4709PH 35 1 1 8 2 1 8 188 85 226 1 885 CDV 400BM6 6B5406PH 40 1 1 8 2 1 8 188 85 281 2 440 CDV 500BM6 6B6462PH 50 1 1 8 2 1 8 188 85 281 2 835 CDV 130BL6 4B2707PL 13 7 8 1 5 8 81 37 144 1 590 CDV 150BL6 4B...

Страница 17: ...le to assist troubleshooting Floating Tube coil design Prebent copper tubes minimize welded joints on internal piping Adjustable head pressure control valves Factory Installed Options Replaceable core liquid line filter driers with sight glasses Liquid line solenoid valves Suction filters Replaceable core suction filters Suction accumulators Oil separators with discharge line check valves Air defr...

Страница 18: ...00180 5 293650 280140 266760 239150 CDD 600BM6 4B3604PH 40 678820 649850 622730 571310 30 569890 546290 523150 476730 25 518410 496570 475180 431820 20 470170 450090 429890 389600 15 423920 405270 386590 349370 5 342580 326630 310890 278110 CDD 660BM6 6B4060PH 40 770100 736570 705660 647170 30 643130 616390 592210 537790 25 585850 559580 535230 486380 20 527550 505170 482450 437980 15 475270 45438...

Страница 19: ...50 94480 78130 CDD 440BL6 6B4060PL 0 312650 297970 283180 254650 10 241300 228460 215670 192460 15 209620 197730 185940 163780 20 181550 170680 159580 138390 30 139100 129450 119730 99570 40 118940 110850 102700 86450 CDD 500BL6 6B4709PL 0 369030 350950 332610 297490 10 285580 270240 254860 226690 15 248670 234530 220520 193970 20 215850 203020 189890 164690 30 166080 154850 143530 119770 40 14228...

Страница 20: ...PH 24 4 147 4 9 6 64 5 80 CONTACT FACTORY FOR SYSTEM ELECTRICAL RATINGS CDD 400BM6 4C2397PH 28 8 176 4 14 0 78 8 100 CDD 440BM6 4B2707PH 30 8 176 4 14 0 83 3 110 CDD 500BM6 4B3139PH 37 8 218 4 14 0 99 1 125 CDD 600BM6 4B3604PH 44 9 245 6 21 0 122 0 150 CDD 660BM6 6B4060PH 50 0 275 6 21 0 133 5 175 CDD 700BM6 6B4709PH 52 6 275 6 21 0 139 4 175 CDD 800BM6 6B5406PH 70 5 350 8 28 0 186 6 250 CDD 110BM...

Страница 21: ...3604PH 60 1 1 8 2 1 8 1 3 8 2 5 8 188 85 269 122 226 3 225 CDD 660BM6 6B4060PH 66 1 1 8 2 1 8 1 3 8 2 5 8 188 85 269 122 226 3 570 CDD 700BM6 6B4709PH 70 1 1 8 2 1 8 1 5 8 3 1 8 188 85 363 165 226 3 770 CDD 800BM6 6B5406PH 80 1 1 8 2 1 8 1 5 8 3 1 8 188 85 363 165 281 4 880 CDD 110BM6 6B6462PH 100 1 1 8 2 1 8 1 5 8 3 1 8 188 85 363 165 281 5 670 CDD 260BL6 4B2707PL 26 7 8 1 5 8 1 1 8 2 1 8 81 37 1...

Страница 22: ...22 Notes ...

Страница 23: ...23 ...

Страница 24: ...ldyoucancounton com Cold You Can Count On Since product improvement is a continuing effort we reserve the right to make changes in specifications without notice For more information on Climate Control products contact your Climate Control Sales Representative or visit us at www coldyoucancounton com CC CUBZTB 0409 001 ...