Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection
from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to
remain illuminated for the requisite time, remedial action must be taken to repair the situation and
once completed, the unit must pass a subsequent test. For more specific information, please refer to
the current edition of the AS 2293.3 Standard.
Ultrablade Maintenance:
LED Lamp Replacement:
•
Use only the LED Strip recommended in the
Spares Parts list of this instruction.
•
Disconnect battery from LED driver pack and
cut cable tie to remove.
•
Disconnect the signal cable from LED strip,
loosen screw and remove the mains driver
pack.
•
Remove 4 self-tapping screws and unclip the
LED strip.
•
Install the new LED strip following the above
procedure in reverse.
Battery Replacement:
•
Use only the battery recommended in the
Spares List on this instruction.
•
Remove the cable ties holding the battery,
un-plug the lead from the battery connector
remove the old battery.
•
Plug the new battery into the battery
connector.
•
Secure the battery using suitable cable ties
Trouble Shooting:
Below are a list of common problems and their
possible causes.
Fault:
The Green LED Test Switch indicator
is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in
emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode,
but only stays on for a short period.
Check:
Battery has been allowed to charge for at
least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions), not Included
–TH version:
Refer to the Technical Label on the Product for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life performance
in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-life
performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz
LP
™
Ultrablade Pro LED Exit
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
195 Chesterville Rd
Moorabbin VIC 3189
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone:
+64
800 548 448
Models:
CUBPRO-yy-xx-zz-ss-ww-vv
Testing:
Options:
Running Man
zz=R
Manual Test
xx = Blank Theatre
yy= TH
Running Man Left Arrow zz=RL
Zoneworks
xx = ZW
Custom Option
ss
Running Man Right Arrow zz=RR
Z/W DATA
xx = DATA Black
vv = BLK Double sided R/M
zz=DS-R
DALI Comp.
xx = DALI
Special Cable Option
Double sided R/M Arrow zz=DS-RAOW
Clevertest
xx = CT
ww = F5C, 5C,
F3C
Vertical R/M Right Arrow zz=VRR
(NOTE: -CT Products supplied with the Clevertest Plus Symbol are activated with Clevertest PLUS
capability. Please refer to the operation guide supplied with the product for details).
Spare Parts:
1550130
BATTERY: LP 3.2V 1500mAh 260mm lead no BRKT.
2310250
Blade Assy t/s Ultrablade Pro LED
2740054
Ultrablade to Ultrablade Pro adapter
CUBPRO-CKIT
Ultrablade Pro, Control Only, LP
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.
Designed in Australia to comply with the requirements
of AS2293.3:2005 and AS/NZ CISPR:15:2017
NOTE: Standard product codes with this symbol
are enabled with Clevertest Plus capability.
Please refer to the operation guide supplied with
the product for details.