1943046
V1.5
January 2019
Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks and DATA Monitored Options
Ultrablades with part numbers CUBPRO-ZW
, CUBPRO-DATA
are fitted with Zoneworks
communications modules (nodes). These fittings are monitored using either Powerline Carrier
Technology that utilises the power cable to provide data communication or a dedicated data cable
to/from data routers installed on a dedicated data trunk connected to a central Server (can also be
connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each Ultrablade and can be commissioned by a single
push of the test switch, or scanning of the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the Ultrablade during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-
way “figure 8” cable and terminal block facilitates the connection
to the DATA network via a multi-drop bus (daisy chain connection). For further information of
installation of a Zoneworks LW system, please refer to the Zoneworks Users Guide and
Commissioning Guide (incl. DATA version)
DALI EM Option
Ultrablades with part numbers CUBPRO
-DALI
are fitted with DALI modules (nodes) that facilitate
connection and integration to 3
rd
Party Lighting Control Systems. Before installing the
CUBPRO-DALI please confirm that the Lighting Control System has the capability to monitor DALI
Emergency Luminaires. The CUBPRO-DALI will be addressed and configured into the control
system by the Lighting Control System Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-
way “figure 8” cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
Networking:
When installing the LP Ultrablade PRO on a monitored network, (
ZONEWORKS, DATA, DALI
) simply
insert the relevant Smart Node PCA.
Installation:
The LP Ultrablade Pro LED Exit (CUBPRO) is a recessed ceiling mount fitting. The CUBPRO can be
attached directly to any solid surface, or to a ceiling tile with the integrated clamping mechanisms. The
CUBPRO comes with an attached Flex and Plug. Please follow the steps below to install the CUBPRO
Exit:
•
If replacing an Ultrablade, an Ultrablade to Ultrablade Pro adapter 2740054 (sold separately) is
required)
•
Create a cut-out (350mm x 48mm) in the mounting surface.
•
Route the power cord to the mains connection and connect the 240VAC supply.
•
Insert the CUBPRO into the ceiling cavity tighten the (4) clamping screws.
•
Alternately, fix the CUBPRO to a solid surface using (4) screws through the surface material.
•
Install the cover plate.
•
Apply power to the fitting and test.
•
If the CTP capabilities are activated, please affix the CTP Status Label to a visible surface.
Solid surface screw points
Pull the trim out at the centre
Lift the decal and slide out
Ceiling Tile
Cover Plate
Luminaire Dimensions:
380mm x 220mm
Cover Plate:
385mm x 67mm
Ceiling Cut-out:
350mm x 48mm
Minimum Depth
80mm
Changing EXIT Legend Inserts
:
The Ultrablade Pro Exit comes with an assortment of standard legends.
1.
To remove the legend, grasp the centre of the bottom trim piece and pull down slightly to expose
the legend edge. See photo.
2.
Grasp the bottom edge of the legend and slide the existing legend out of the blade, while working
the edges out along the sides.
3.
Slide the new legend into the blade, ensuring to fit the edges into the sides then slide the legend to
the top of the blade. Insert one bottom corner then the other. Slide the legend down into the bottom
trim.
Clamping screws
Clamping screws
Insert corners (1&2)
then slide up (3)
Insert corners (4&5), then slide down