Installation:

 

This LP Emergency batten can be wall or ceiling mounted. 

 

 

Refer Images below for the mounting hole, cable access and other dimensions. 

 

Remove the diffuser. 

 

Remove the cover plate and disconnect the LED strip connector. Unhook the lanyard 

 

Position the batten in the desired location. 

 

Mark out the fixing points on the mounting surface. 

 

Install appropriate fixing hardware. 

 

Route power supply cables through the access hole at the rear of the fitting or the ends if using 

surface conduit (punch out the knock-outs in the plastic end caps) 

 

Fasten the batten to the surface. 

 

Terminate the supply cable to the terminals marked A

EM

, N, A

SW

 and E (240V AC/50Hz) 

 

Attach the cover plate to lanyard, Re-connect the LED strip connector and Re-attach the cover 

plate onto the body of the batten. 

 

Re-install the diffuser  

 

If the 

CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

Dimensions: 

 

 

 

Testing:

 

When the LP batten unit is connected to the un-switched active, it must be allowed to charge the battery 

for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following 

tests: 

 

 

The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The 

results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all 

times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the 

situation and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 

Fault:   The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 

for –TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 

discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 

performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-

life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 