Initial Testing:

 

 
When the LWPLIFEz-PRO-xx-yy-WM-ss unit is connected to the un-switched active, it must be allowed to 
charge the battery for at least 24 hours. The emergency lamp only illuminates during a power failure. 
Conduct the following tests: 
 

 

During the first commissioning test the emergency lamp must illuminate for at least 2 hours after 
disconnection from the main supply. The results of all tests are required to be recorded in a service 
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time, 
remedial action must be taken to repair the situation and once completed, the unit must pass a 
subsequent test.   

 

To test, remove the screws holding the glass cover to the fitting to access the test button. 

 

Press and hold Test Button check that the emergency lamp is On. 

 

Alternately, turn off Mains Supply to the fitting. Verify the lamp is on. 

 

Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off 
(Non-maintained operation). 

 
 

Below are a list of common problems and their possible causes: 

 

Fault:   

The Green LED indicator is not illuminated.

 

Check:    A.C. is connected and is turned on. 
 

Battery is connected. 
Test Switch for damage. 
 

Fault:   

Lamp does not illuminate in emergency mode. 

 

Check:    A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions):

 

 

 

Refer to the Technical Label for classification information. 
 
 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or 
“cycled”. The Li-ion battery in the Lifelight has been selected to give excellent long-life performance in a 
controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life 
performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, 
are specifically EXCLUDED from Clevertronics warranty terms. 
 
 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 

Installation: 

 

This Wall Mount Weatherproof Lifelight Pro Emergency Luminaire must be installed on a solid surface. 

 

Loosen the grub screw and remove the mounting plate from the fitting. 

 

Locate the installation position. 

 

Using the mounting plate as a template, mark out the holes required to mount. 

 

Position the plate to the surface while routing the power cable through the gland. 

 

Use suitable fixings to fasten the mounting plate to the mounting surface. 

 

Route and terminate the supply cables to the L, N & E terminals in the gear tray. (in the case of the 
–DALI or –DATA fittings terminate the DALI or DATA cable to the terminals marked Da Da or 
DATA). 

 

Reinstall the main assembly and secure with the grub screws. 

 

Apply power to the fitting and check operation. 

 

If the CTP capabilities are activated, please affix the CTP status Label to a visible surface.   

 
 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 
relevant Smart Node PCA. 
 

 

 
 
 