Cleveland 24-CGM-200 Скачать руководство пользователя страница 14

Replace the

 on/off rocker

switch

Yes

Connect power

to steamer.

No

Is the red light on

in the power

switch?

Is there power to

the steamer?

Is there water in

the sight glass?

Yes

See

Steamer won't

fill.

No

Yes

PROBLEM:

Gas Boiler won't

build pressure

No

Boiler won't build

pressure

Is the red "LOW

Water"  light on?

Yes

Is the red "LOW

Water"  light on

with a jumper from

terminals LOW

and C on the water

board?

Replace the

water board.

Is the Amber light

on in the reset

switch?

No

Is there 120 VAC

between

terminals L2 and

HTR on the water

board?

Yes

Repair

 or Replace the

probe circuit.

No

Is there 120 VAC

between terminals

L2 and HTR on the

water board with a

jumper between

LOW and C?

Is there 120 VAC

to terminal 2 on

the R1 relay?

Repair

 or Replace the

probe circuit.

Replace the
water board

Replace the

Reset switch

Yes

After depressing
the reset switch,

does the Amber

light go off?

Does this boiler

have the optional

Secondary  Low

Water Cut Out?

With the High

Limit pressure

switch

temporarily

bypassed, does

the Amber light go

off when the reset

switch is

depressed?

Yes

No

No

Yes

No

Replace

 the high limit

pressure

 switch

With the SLW CO

switch

temporarily

bypassed, does

the Amber light go

off with the reset

switch depressed?

No

Yes

Yes

Replace the

SLWCO switch

With a jumper

from terminal 6 to
4 on the R2 relay,

does the Amber

light go out with
the reset switch

depressed?

No

No

Replace the

relay.

Yes

Yes

Is there 120 VAC

to the primary of

the 24 VAC

ignition

transformer?

No

Yes

Replace the R1

relay

No

Yes

Is there 120 VAC

to the primary of

the ignition

transformer with

the operating

pressure switch

temporarily

bypassed?

No

Replace the R1

relay

Replace

 the operating

pressure

switch

Is there 24 VAC at

the secondary  of

the ignition

module?

Yes

Is there flame at

the burner?

Yes

With

flame and water the

Boiler is making

steam.  Check for

leaks.

Is there allot of

steam coming out

the drain?

Yes

Replace the

steam trap

Yes

No

See 

Boiler

won't ignite.

No

Replace the

ignition

transformer

No

No

Yes

No

Содержание 24-CGM-200

Страница 1: ... technical and technological changes revisions or updates Cleveland Range LLC assumes no liability or responsibility regarding errata changes revisions or updates Qualified Cleveland Range LLC Authorized Service Representatives are obligated to follow industry standard safety procedures including but not limited to OSHA regulations and disconnect lock out tag out procedures for all utilities inclu...

Страница 2: ... and the set time 115 VAC is sent through the optional door switch 115 VAC is sent to the condensate solenoid and cold water is sent to the condensate spray nozzle 115 VAC is sent to the steam solenoid and steam is sent to the cooking cabinet There the steam is directed around the product and pulled down the drain by the condensate spray When the cooking compartment reaches 193 degrees internally ...

Страница 3: ......

Страница 4: ...switch 115 VAC is sent to the condensate solenoid and cold water is sent to the condensate spray nozzle 115 VAC is sent to the steam solenoid and steam is sent to the cooking cabinet There the steam is directed around the product and pulled down the drain by the condensate spray 3 When the timer counts down in the timed position 115 VAC is removed from the condensate circuit 115 VAC is removed fro...

Страница 5: ......

Страница 6: ...Cleveland Range LLC 1333 East 179th St Cleveland Ohio U S A 44110 Ph 1 216 481 4900 Fx 1 216 481 3782 Visit our Web Site at www clevelandrange com ...

Страница 7: ...ater indicator light 3 When the momentary amber switch is depressed 115 VAC is sent to the R1 relay closing it x The normally closed R1B contacts open de energizing the amber light x The relay latches itself through contacts 3 and 5 with a jumper to the coil x If either the high pressure switch opens or the low probe circuit on the water level board opens then the latch circuit opens x When the wa...

Страница 8: ...ized x When the pressure drops below the set point the heat circuit is energized and the heat process begins again 7 Water continues to fill until the high probe is grounded x When the high probe is grounded the WF terminal on the water level board is de energized x The fill solenoid closes until the high probe is ungrounded for 5 seconds x If the water level drops below the high probe for more th...

Страница 9: ...o the low probe shorting it to ground x 115 VAC is removed from the IND terminal and the low water indicator light is de energized x If the low water cut off float switch opens the low water indicator light re energizes x 115 VAC is sent from the HTR terminal to the normally open contacts of R2B x With water in the unit and the R2 relay energized 115 VAC is sent through the normally closed contact...

Страница 10: ...W C 5 The water in the boiler is heated to steam x As steam is generated and pressure builds the air is pushed out through the steamtrap x When steam goes through the steam trap and heats it to 192 degrees it closes 6 Pressure builds in the boiler to the set point x The operating pressure switch opens and the heat circuit is de energized x When the pressure drops below the set point the heat circu...

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ...e the optional Secondary Low Water Cut Out With the High Limit pressure switch temporarily bypassed does the Amber light go off when the reset switch is depressed Yes No No Yes No Replace the high limit pressure switch With the SLWCO switch temporarily bypassed does the Amber light go off with the reset switch depressed No Yes Yes Replace the SLWCO switch With a jumper from terminal 6 to 4 on the ...

Страница 15: ...ater leaving the fill solenoid Replace wiring to drain solenoid Does the steamer have the optional intermittent blowdown timer Replace the wiring to the intermittent blowdown timer Is there 120 VAC between terminals 2 3 on the timer Replace the intermittent blowdown timer Is there 120 VAC across the coil of the drain valve Is water draining from the generator If water is leaving the fill solenoid ...

Страница 16: ...placing the ground wire to the burner ground terminal is there 1 5 micro amps DC to the ignition module No Is there flame at the burner Yes Yes No With spark and gas there should be fire Recheck the gas pressure and burners and igniter Yes Yes Replace the ignition wire No Boiler won t heat start PROBLEM Gas boiler won t ignite PROBLEM Gas Boiler Overfills Boiler over fills With the HI probe emerse...

Страница 17: ...ler Stops Producing Steam Boiler stops steaming Does the amber light in the reset switch come on Is the temperature sensitive dot surrounded by a yellow circle on the water board white Replace the water board It has reached a temperature of over 180 degrees Yes No The ignition module has gone into lockout See Boiler won t ignite Does boiler have the optional Secondary Low Water Cut Out Yes Are the...

Страница 18: ... on the TDS timer to prevent the purge from coming on To open the hand hole plate loosen and remove the nut and bar across the generator opening Place the end of a two x four on the hand hole plate Rap the end of the wood with a hammer in various places until the plate and gasket fall inside the generator Remove any scale build up that can be taken out by hand or with a small vacuum cleaner IF THE...

Страница 19: ... 5 DO NOT PRESS THE AMBER STEAM SWITCH THIS CHEMICAL WORKS BEST WHEN COLD STEP 6 Wait 1 2 hours to allow for descaling of the generator Drain the generator by turning off the red POWER switch The drain and fresh water solenoid valves will open for three minutes allowing the generator to flush out After draining fill the generator with fresh water and repeat the flush process by turning off the pow...

Страница 20: ...red power switch to fill the generator and then the amber switch when the light comes on After twenty 20 minutes the generator should have steam in it Check for steam leaks around the hand hole If any leaks are found repeat the process for replacing the gasket ...

Страница 21: ...1333 East 179th Street Cleveland Ohio 44110 Phone 216 481 4900 Fax 216 481 3782 ...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Отзывы: