MAINTENANCE
I115SS
Rev. 001
07/10/14
42/49
5.2.1 HYDROMETRY
In order to check the batteries hydrometry the operator has to follow the instructions below:
By means of a hydrometre draw a small quantity of electrolyte so that the floater reaches the
surface;
Make sure that the floater inside the hydrometre is not blocked;
For a new measurement, after having filled the batteries with distilled water, the operator has to wait
until the liquid inside each battery becomes homogeneous.
5.2.2 WATER FILLING UP
Fill distilled water up in each battery cell before the recharge. The liquid inside the batteries has
to be of 6 mm. over the plates;
The operator has to repeat the same operation every time the level decreases (every week).
5.2.3 CHARGE LIMITS
It is not necessary to recharge the batteries if the hydrometry, after a work day, is not under 1,24 (28 Bè).
The highest suggested temperature is 45°C. If the electrolyte temperature increases more than 10/12 °C
compared to the outside temperature, the batteries can be overcharged.
5.2.4 OFF DUTY OR INACTIVE BATTERIES
Inactive batteries looses their automatically their charge. If batteries do not continually work, the operator has
to:
Charge the batteries once a month with a ‘final’ stream intensity until gas is spread and the
batteries voltage and weight are constant for 3-4 hours. This operation has to be done even if
the absolute weight is high;
Keep the batteries in a dry room.