Industrial Ethernet Unmanaged
7
Rear Panel View with DIN rail and Wall Mounting Brackets
(common rear view, may vary with model)
Models
SSF-1x2-RUGGED
SSF-1x4-RUGGED
SSF-1x4POE-RUGGED
DIN Rail Mounting Procedure
All Industrial switches from the SSF-RUGGED series have DIN rail bracket mounted
from factory to the rear panel of the unit. If wall mounting is needed, first remove
the DIN rail bracket. If DIN rail bracket needs to be reattached, make sure the
spring is located on top position when unit is vertical.
Step 1
Step 2
Hold unit as in below image, making
sure top of bracket with spring falls
onto the top edge of TS-35 DIN rail.
Rotate and snap the unit onto the DIN
rail by pushing the bottom unto the TS-
35 DIN rail. Unit will be secured to rail.
To remove unit from rail, repeat procedure in reverse. Start by pulling out the
bottom of unit from the DIN rail.