Prometha
™
Installation
750-441
27
Hawk 4000 V2
Point Name
Data Type
1
Drive Fault
BI
2
Modbus Comm Error
BI
3
Lo Water
BI
4
Burner Control Alm
BI
5
Boiler Limits Open
BI
6
Hi Stack Temp Alm
BI
7
Hi Stack Temp Shutdown
BI
8
External Interlock
BI
9
I/O module fault
BI
10
Steam Sensor Fail
BI
11
Air Actuator Out Of Pos Alm
BI
12
NG Actuator Out Of Pos Alm
BI
13
F/A Ratio Controller Fault
BI
14
No Fuel Selected
BI
15
Low ControlLogix Battery
BI
16
Non Recycle Limit Relay Fail
BI
17
Recyle Limit Relay Fail
BI
18
Rem Modulation Signal Fail
BI
19
Header Pressure Sensor Fail
BI
20
Temp Channel 0-5 Fail
BI
21
Lo O2 Alm
BI
22
Hi Limit Alm
BI
23
ALWCO
BI
24
Lo Gas Pressure/Lo Oil Temp
BI
25
Hi Gas Pressure/Hi Oil Temp
BI
26
Lo Oil Pressure
BI
27
Hi Oil Pressure
BI
28
Oil Drawer Switch Not Made
BI
29
Lo Atomizing Air Pressure
BI
30
Lo Combustion Air Pressure
BI
31
Stack Damper High Pressure
BI
32
AUX Alm 2
BI
33
Blower On
BI
34
Purge Input
BI
35
Release To Modulate Input
BI
36
Lo Fire Switch
BI
37
Hi Fire Switch
BI
38
Ready to start/Limits Closed
BI
39
External Start Interlock
BI
40
ALFCO
BI
41
Pilot
BI
42
Main Fuel Valve Open
BI
43
Fuel 1 Selected
BI
44
Fuel 2 Selected
BI
45
Heart Beat To BMS
BI
46
LWCO Shutdown
BI
47
Rem Enable Input
BI
48
Burner Switch
BI