ClearFox CU-M Скачать руководство пользователя страница 7

ClearFox®Control Unit CU-M

7

 

C

ONNECTING TO 

W

I

-F

I

 

The 

ClearFox®Control Unit CU-M 

can be operated and monitored via Wi-Fi. All

settings can be done comfortably in your browser (smartphone, tablet, PC).  

-

SSID: WWTP-Controller

-

Wi-Fi password: 12345678

-

IP address (must be entered into the browser address line (=where you’d type

www.google.com

): 

http://192.168.117.1/

o

Username: service

o

Password: 

1111

 (same as service menu PIN)

In case these parameters shall be changed, please refer to the 

Network Settings

 page: 

Figure 2: Wi-Fi - Access Point settings 

Please do not forget to push 

Apply Wi-Fi Settings

 (control unit restarts).  

The 

ClearFox®Control Unit CU-M

 can run Wi-Fi in Access-Point (AP) and in Station

 

Mod

(ST

)

-

AP: Wi

-

Fi hotspot without internet connection (intranet only)”

-

ST: Connection to another Wi-Fi hotspot or router (e.g. your company Wi-Fi), often used

to connect the 

Sequetrol

® IoT

 to the public internet (e.g. for telemetry)

7.1

 

C

ONNECTING THE CONTROL UNIT TO THE INTERNET VIA 

W

I

-F

(ST

 MODE

The control unit can be run simultaneously in 

Access Point

 (AP) and 

Station

 (ST) mode. 

-

Access Point

 

mode means, the control unit behaves as a “Wi

-Fi hotspot

”. You can

connect with any device and view the internal webpages.

-

Station

 

mode

 means, the control unit connects to another Wi-Fi network (mostly with

internet access).

Содержание CU-M

Страница 1: ...1 Quick Start Guide ClearFox Control Unit CU M...

Страница 2: ...ed Bed 6 6 5 Drippling filter D Tropfk rper 6 7 Connecting to Wi Fi 7 7 1 Connecting the control unit to the internet via Wi Fi ST mode 7 8 Alarm handling 8 9 Process overviews 8 9 1 Air SBR 8 9 1 1 P...

Страница 3: ...ClearFox Control Unit CU M 3 12 2 Transfer via USB 16...

Страница 4: ...where you d type www google com http 192 168 117 1 o Username for service login service o Password 1111 same as service menu PIN 3 INTRODUCTION The ClearFox Control Unit CU M platform is a powerful fr...

Страница 5: ...t the underside of the printed circuit board and close to the mains supply connectors and the fuse mains voltage 230 V Before removing the casing cover it is necessary to pull the mains supply connect...

Страница 6: ...jection Aerator Connected to the electric socket of the ClearFox Control Unit CU M Out 5 electric socket Sludge return Pump Out 3 Valve Out 3 Blower BonFlash alarm beacon is connected to the terminals...

Страница 7: ...not forget to push Apply Wi Fi Settings control unit restarts The ClearFox Control Unit CU M can run Wi Fi in Access Point AP and in Station Mode ST AP Wi Fi hotspot without internet connection intra...

Страница 8: ...deactivates the Buzzer and the BonFlash output The red LED remains on and the last alarm remains in the Status Screen until the reason for the alarm is gone e g float switch is down again or until th...

Страница 9: ...Eco mode o Aeration o Level measurement via Filling If above switching level 1 normal o Each 6 eco cycles frequency can be changed At least one normal mode 9 1 2 Water level measurement Water level m...

Страница 10: ...re as it cannot suck anymore water 3 Sludge return for some 60s to increase the level in the pretreatment so that the filling airlift can pump properly again 4 Filling for 20s the pressure at this min...

Страница 11: ...over DI1 open Eco Via Sludge Pump ON 10s OFF 14 50min or until DI1 closed On timeout step time over DI1 open Eco o Denitrification 0 40min ON 9 20min OFF 60min Total o Aeration 8min ON 12min OFF 9 5h...

Страница 12: ...ssure limits 7 350mbar for Blower applied Pump Out 3 Current limits 300 1800mA for pump applied 9 3 ONE TANK SBR 9 3 1 Process steps For the level measurement overfill alarm a manual calibration must...

Страница 13: ...ease ask PPU in case you want to activate it Time taken from the settling time example Settling 2h sludge 2min settling will be 1 58h in reality and sludge 2min sludge return after settling can be dea...

Страница 14: ...ower applied Via sludge pump Out 3 Current limits for pump 300 1800mA applied CLEARWATER Blower valve Out 1 2 Current limits for Blower 250 900mA valve 50 150mA applied Generic pressure limits 7 350mb...

Страница 15: ...mA valve 50 150mA applied Generic pressure limits 7 350mbar for Blower applied Via sludge pump Out 4 Current limits for pump 300 1800mA applied CLEARWATER ON DAY OFF DAY ON NIGHT OFF NIGHT ON HOLIDAY...

Страница 16: ...here click on Start update process done 12 2 TRANSFER VIA USB Please mind that the batteries must be connected Please record the pkg Pack file into the root folder of a common USB stick formatted wit...

Отзывы: