FieldSmart
®
FiberFlex 2000
Installation Manual
_________________________________________________________
Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
94
Step 2:
Install a new controller module as follows:
a.
Insert the new controller module partially into the vacated slot, allowing access to the (5) alarm interface
connectors.
b.
Connect the alarm wires to the alarm input and output positions (see table below for guidance).
• Push the orange tab in, and then insert the alarm wire in the connector.
• Holding the wire in place, release the orange tab.
c.
Connect the temperature probe cable as follows:
•
Connect the red alarm wire to P1 PIN 6 (+).
•
Connect the black alarm wire to P1 PIN 6 (-).
d.
Push firmly on the module to seat it in the slot.
When the controller operational indicator is lit, it has completed its initialization and is ready to operate on the default set-
tings.
Note:
For instructions on programming the controller module, see the Eltek Smartpack A Controllers User Guide.
The Eltek Smartpack S controller module is equipped with four alarm interface connectors. The alarm connector cabling
scheme follows.